Air Quality — The Air Quality set point is used to configure
the IAQ set point for the zone controller if optional controlled
ventilation support is used.
Air Quality

Units

none shown (ppm

(ppm):

implied)

Range

0 to 5000

Default Value

850

Delta Airflow — The Delta Airflow set point is used to con-
figure the Delta Airflow set point for the zone controller if the
zone pressure control option is used. If a negative pressure is
desired, configure the value as a positive delta.
Delta Airflow:

Units

cfm

Range

-9999 to 9999

Default Value

0

Service Configuration Selection Screen —

The

Service Configuration Selection screen is a menu of Service
screens which can be accessed by the user. The following
screens are available: Airflow Service Configuration, Terminal
Service Configuration, Option Service Configuration, and Sec-
ondary Damper Service Configuration.
AIRFLOW SERVICE CONFIGURATION SCREEN —
The Airflow Service Configuration Table is used to configure
the pressure independent and backup pressure dependent set
points. See Table 9.
Pressure Independent — Pressure Independent (PI) set points
should be configured for pressure independent operation
applications.

Cool Minimum (PI) — This configuration is the minimum
airflow the terminal will control to when the equipment is in
Cooling mode (or Fan Only mode) or free cooling. The space
requirements for cooling must be at a minimum, or the terminal
is a fan powered terminal and the space requirements are for
heat.
Cool Minimum:

Units

CFM

Range

0 to 9999 (Limited by

the High Velocity pressure limit alarm)
Default Value

0

Cool Maximum (PI) — This configuration is the maximum
airflow the terminal will control to when the equipment is in
Cooling mode (or Fan Only mode) or free cooling and the
space requirements for cooling are at a maximum.
Cool Maximum: Units

CFM

Range

0 to 9999 (Limited by

the High Velocity pressure limit alarm)
Default Value

4000

Terminal Reheat (PI) — This configuration is for single duct
units with ducted reheat. The desired airflow is configured at
which the reheat will provide optimum performance. This val-
ue is compared to the Minimum Cool value and the greater of
the two values is used to determine the airflow set point.
Terminal Reheat: Units

CFM

Range

0 to 9999 (Limited by

the High Velocity pressure limit alarm)
Default Value

0

Table 8 — Set Point Screen

Table 9 — Airflow Service Configuration Screen

DESCRIPTION

DEFAULT

POINT NAME

Set Points

Occupied Heat

70.0 F

OHSP

Occupied Cool

74.0 F

OCSP

Unoccupied Heat

55.0 F

UHSP

Unoccupied Cool

90.0 F

UCSP

Occupied HIgh Humidity

60.0 %

ORHH

Unoccupied High Humidity

100 %

URHH

Air Quality (ppm)

850 ppm

AQSP

Delta Airflow

0 cfm

DCFM

DESCRIPTION

DEFAULT

POINT NAME

Pressure Independent

Cool Minimum

0 cfm

COOLMIN

Cool Maximum

4000 cfm

COOLMAX

Terminal Reheat

0 cfm

REHEAT

Heat Minimum

0 cfm

HEATMIN

Heat Maximum

4000 cfm

HEATMAX

Parallel Fan On

0 cfm

FNONCFM

Dual Duct CV Airflow

4000 cfm

DDCVFLOW

Pressure Dependent

Cool Minimum Position

0 %

CMINPOS

Cool Maximum Position

100 %

CMAXPOS

Reheat Minimum Position

0 %

REMINPOS

Heat Minimum Positon

0 %

HMINPOS

Heat Maximum Position

100 %

HMAXPOS

Deadband Percent

12.5 %

DB_PCT