Fig. 22 — humidity sensor wiring – Carrier 33ZCFANTRM User Manual

Page 27

background image

27

3. Connect the other end of the communication bus cable

to the terminal block labeled CCN in the zone control-
ler of the first air terminal. Following the color code
in Table 3, connect the Red (+) wire to Terminal 1.
Connect the White (ground) wire to Terminal 2. Con-
nect the Black (–) wire to Terminal 3.

4. Connect additional zone controllers in a daisy chain

fashion, following the color coded wiring scheme in
Table 3. Refer to Fig. 25.

NOTE: The communication bus drain wires (shield) must
be tied together at each zone controller. If the communica-
tion bus is entirely within one building, the resulting contin-
uous shield must be connected to ground at only one single
point. If the communication bus cable exits from one build-
ing and enters another building, connect the shields to
ground at a lightning suppressor in each building where the
cable enters or exits (one point only).

+

-

499

RESISTOR

(SUPPLIED

W/SENSOR)

HUMIDITY SENSOR

RED

WHITE

BLACK

3 CONDUCTOR
20 AWG CABLE

SHIELD
(IF USED)

35 in-lb (4 Nm)
80...110s

H F 2 3 B J 0 4 2

M a d e i n S w i t z e r l a n d

b y B e l i m o A u t o m a t i o n

1

0

yel

blu

ora

WIP

5K

LISTED
94D5

TEMP. IND. &
REG. EQUIP.

UL

Class 2 Supply

L R 9 2 8 0 0

NEMA 2

24VAC/DC
50/60Hz

3VA

2W

COM

1

2

3

blk

red

wht

+24V

RH/IAQ

GND

Fig. 22 — Humidity Sensor Wiring