background image

31

4. If the terminal is a parallel or series powered fan box,

force the Fan Override to Enable. If the damper is open
it may have to be repositioned to the proper position
depending on the box type. Damper percent change
will be displayed. After the damper is positioned cor-
rectly, the fan relay should energize and the fan should
run for a few seconds.

5. Make sure the fan runs and the Fan Override decision

returns to disabled to ensure the fan is wired correctly
for proper operation.

6. Force the Heating Override to Enable. If the unit is a

single duct unit, this must be done with the primary
terminal at reheat set point. The damper will modulate
to maintain the terminal reheat CFM. The heat outputs
will be commanded to provide maximum heat. If the
unit is a fan powered terminal, the fan must be on.

NOTE: The CFM settings can be found under service con-
figuration in the table AIRFLOW.

CONFIGURATION

The following sections describe the computer configuration

screens which are used to configure the zone controller. The
screens shown may be displayed differently when using differ-
ent Carrier software.

Points Display Screen —

The Points Display screen

allows the user to view the status of the air terminal controller
points. See Table 4.
TERMINAL MODE — The terminal mode is determined by
the equipment mode as reported by linkage and space require-
ments determined by space temperature and set points. The
ZEROCAL and COMMISS modes are the result of the activat-
ing the commissioning maintenance table to perform terminal
testing and commissioning.
Terminal Mode:

Display Units

ASCII

Default Value

COOL

Display Range

HEAT, COOL, VENT,

FAN AND VENT, DEHUMID, WARM-
UP, REHEAT, PRESSURE, EVAC, OFF,
ZEROCAL, COMMISS
Network Access Read only

TERMINAL TYPE — Terminal type is the confirmation of
the terminal type configuration in the SERVCONF Service
Config table.
Terminal Type:

Display Units

ASCII

Default value

SINGLDUCT

Display Range

SINGLDUCT, PAR

FAN, SER FAN, DUALDUCT
Network Access Read only

CONTROLLING SETPOINT —

Controlling Setpoint will

display either the heating master reference or the cooling mas-
ter reference depending upon what mode the terminal is in. The
display will default to the heating master reference and display
the last controlling master reference when in neither heating
nor cooling.
Controlling
Setpoint

Display Units

F (C)

Default Value:

–40

Display Range:

–40 to 245

Network Access: Read only

SPACE TEMPERATURE — Space temperature from 10 k

thermistor (Type III) located in the space.
Space
Temperature:

Display Units

F (C)

Default Value

-40.0

Display Range

-40.0 to 245.0

Network Access Read/Write

PRIMARY AIRFLOW — Volume of primary air calculated
for pressure reading from the velocity pressure pickup probe
located in the input collar of the air terminal.
Primary Airflow: Display Units

cfm

Default Value

0

Display Range

0 to 9999

Network Access Read/Write

PRIMARY DAMPER POSITION — Damper position per-
cent range of rotation determined by the transducer calibration
procedure. The zone controller is designed be used on dampers
with any range of rotation.
Primary Damper
Position:

Display Units

% open

Default Value

0

Display Range

0 to 100

Network Access Read only

Table 4 — Points Display Screen

DESCRIPTION

DEFAULT

POINT NAME

Terminal Mode

COOL

MODE

Terminal Type

SINGLDUCT

TYPE

Controlling Setpoint

-40.0 F

CNTSP

Space Temperature

-40.0 F

SPT

Primary Airflow

0 cfm

PRIFLO

Primary Damper Position

100 %

DMPPOS

Supply Air Temperature

0.0 F

SAT

Local Heating Capacity

0 %

HCAP

Terminal Fan

Off

FAN

Relative Humidity

0 % RH

RH

Air Quality (ppm)

0 ppm

AQ

Secondary Airflow

0 cfm

SECFLO

Primary Air Temperature

0.0 F

PATEMP

Heat

Dsable

HEAT

801