A. C. MODULAR GENERATOR SYSTEM
Page 32 of 49
Note: If you override the system and command it to operate with a faulty
temperature sensor, the system may overheat and you will void the system’s
warranty.
11.
If the system determines the generator output voltage is out of range, it will begin
displaying an alarm. This fault can be detected only when the generator is
operating, and will automatically shut down the generator after 30 minutes unless
the shutdown is overridden. To override the shutdown, perform the following steps:
Note: The alarm must be active for this procedure to work.
Step a: Press Mode to
cause
rvn
and the
y
and
n labels to appear.
Step b: Press On/Off to
answer “yes” and make
the next screen appear.
Example of Command & Control Center
in voltage range fault override
Figure 25
a. From the Normal mode display, press Mode, as if you wanted to display the oil
temperature. The screen shown in Figure 25 will be displayed instead, asking if
you want to “Rvn [with] bad UOLt[age].”
b. Note the y and n labels below the Mode and On/Off switches. Press the On/Off
switch to answer “yes” and proceed to the next screen, or press Mode to answer
“no” and proceed to the oil temperature display.