Smart Power Systems LR Series User Manual
Page 29

Smart Power
®
Systems
A. C. MODULAR GENERATOR SYSTEM
Page 28 of 49
8.
If the system measures a hydraulic oil temperature that exceeds 175°F (79°C), the 
system will begin displaying an alarm. If the system measures a hydraulic oil 
temperature that exceeds 180°F (82°C), the generator will automatically shut down 
in 30 minutes unless the shutdown is overridden. If the temperature of the hydraulic 
oil is measured at or above 220°F, the system will immediately shut down whether 
or not the high temperature oil warning is overridden. To override the shutdown, 
perform the following steps: 
Note: The system must measure a hydraulic oil temperature that exceeds 180°F for 
this procedure to work. 
 
Step a: Press Mode to 
cause
rvn
and the
y
and
n labels to appear.
Step b: Press On/Off to 
answer “yes” and make 
the next screen appear. 
Example of Command & Control Center in hot oil fault override
Figure 19
 
 
a. From the Normal mode display, press Mode, as if you wanted to display the oil
temperature. The screen shown in Figure 19 will be displayed instead, asking if 
you want to “Run hot.” This screen will also be displayed if you attempt to start 
the generator with the condition present. 
 
b. Note the y and n labels below the Mode and On/Off switches. Press the On/Off 
switch to answer “yes” and proceed to the next screen, or press Mode to answer 
“no” and proceed to the oil temperature display. 
 
 