a. From the Normal mode display, press Mode, as if you wanted to display the oil
temperature. The screen shown in Figure 21 will be displayed instead, asking if 
you want to “Run [with the] Oil Lo[w].” This screen will also be displayed if you 
attempt to start the generator with the condition present. 
 
b. Note the y and n labels below the Mode and On/Off switches. Press the On/Off 
switch to answer “yes” and proceed to the next screen, or press Mode to answer 
“no” and proceed to the oil temperature display. 
 
 
Step c: Press On/Off to 
answer “yes” and 
override the shutdown. 
Example of Command & Control Center
in low oil fault override confirmation
Figure 22
 
 
c. If your answer was “yes” in the previous step, the confirmation screen shown in
Figure 22 will be displayed. Again note the y and n labels below the Mode and 
On/Off switches. Press the On/Off switch to answer “yes” and override the 
shutdown. Press Mode to answer “no” and proceed to the oil temperature 
display. 
 
 
Note: If you override the system and command it to operate with insufficient 
hydraulic fluid, the system output power may degrade and you will void the 
system’s warranty. 
 
10. 
If the system determines the hydraulic fluid temperature sensor is faulty, it will begin 
displaying an alarm. If the generator was running when the fault is detected, it will 
automatically be shut down in 30 minutes unless the shutdown is overridden. To 
override the shutdown, perform the following steps: 
Note: The alarm must be active for this procedure to work. 
 
 