Smart Power Systems LR Series User Manual
Page 31
Smart Power
®
Systems
A. C. MODULAR GENERATOR SYSTEM
Page 30 of 49
a. From the Normal mode display, press Mode, as if you wanted to display the oil
temperature. The screen shown in Figure 21 will be displayed instead, asking if
you want to “Run [with the] Oil Lo[w].” This screen will also be displayed if you
attempt to start the generator with the condition present.
b. Note the y and n labels below the Mode and On/Off switches. Press the On/Off
switch to answer “yes” and proceed to the next screen, or press Mode to answer
“no” and proceed to the oil temperature display.
Step c: Press On/Off to
answer “yes” and
override the shutdown.
Example of Command & Control Center
in low oil fault override confirmation
Figure 22
c. If your answer was “yes” in the previous step, the confirmation screen shown in
Figure 22 will be displayed. Again note the y and n labels below the Mode and
On/Off switches. Press the On/Off switch to answer “yes” and override the
shutdown. Press Mode to answer “no” and proceed to the oil temperature
display.
Note: If you override the system and command it to operate with insufficient
hydraulic fluid, the system output power may degrade and you will void the
system’s warranty.
10.
If the system determines the hydraulic fluid temperature sensor is faulty, it will begin
displaying an alarm. If the generator was running when the fault is detected, it will
automatically be shut down in 30 minutes unless the shutdown is overridden. To
override the shutdown, perform the following steps:
Note: The alarm must be active for this procedure to work.