WARNING:
 
Never exceed 1500 RPM engine speed when the PTO is engaged. Doing so will void 
the system’s warranty. 
 
Do not approach a running A.C. modular generator when wearing long, loose items 
such as hair, jewelry, ties, clothing, etc. Direct contact with a rotating drive shaft 
can cause serious personal injury and/or damage to the system. 
 
 
1. 
Obtain the following hoses of the necessary length for the installation:
 
a) Pump inlet hose: 1” SAE 100R1AT-16 hose (use Parker hose ends P/N 10643-
16-16). Note: Maximum hose length is 20’.
b) Pump outlet hose: 5/8” SAE 100R13-10 rated to 4000 PSI (use Parker hose
ends, part number 10671-10-10). Note: Maximum hose length is 20’.
WARNING:
 
Do not install hose ends until proper hose length has been determined. 
 
Never install a hose in a location where it will rub against another surface or 
abrasion member. 
 
Do not position hoses with tight bend radii. Consult the hose manufacturers 
installation guidelines. Tight bends may kink and cause serious damage to the 
system and will void the system’s warranty. 
 
Use caution when tightening the hose ends to prevent the hose from becoming 
twisted. 
 
Never install a 90° fitting at the pump inlet or outlet. Avoid the use of flow 
restricting fittings. 
 
Do not form loops in the hose that may collect air or kink. Run hoses as straight as 
possible (but not taut) between connections. 
 
Do not exceed hose lengths of 20 feet. 
 
 
 