3 setting the digital filter parameters, 8 analog output calibration, Setting the digital filter parameters – Rice Lake SURVIVOR 420HE Hostile Environment - Installation Manual User Manual
Page 50: Figure 7.8 46 for an

46
420HE Installation Manual
7.7.3
Setting the Digital Filter Parameters
Fine-tuning the digital filter parameters greatly 
improves indicator performance in heavy-vibration 
environments. Use the following procedure to 
determine vibration effects on the scale and optimize 
the digital filtering configuration.
1. In setup mode, set all three digital filters
( D I G F L 1 , D I G F L 2 , D I G F L 3 ) t o 1 . S e t 
DFTHRH to NONE. Return indicator to 
normal mode.
2. Remove all weight from the scale, then watch
t h e i n d i c a t o r d i s p l a y t o d e t e r m i n e t h e 
magnitude of vibration effects on the scale. 
Record the weight below which all but a few 
readings fall. This value is used to calculate the 
DFTHRH parameter value in Step 4.
For example, if a heavy-capacity scale 
produces vibration-related readings of up to 50 
lb, with occasional spikes to 75 lb, record 50 lb 
as the threshold weight value.
3. Place the indicator in setup mode and set the
digital filters (DIGFLx) to eliminate the
v i b r a t i o n e ff e c t s o n t h e s c a l e . ( L e a v e 
DFTHRH set to NONE.) Reconfigure as 
necessary to find the lowest effective values 
for the DIGFLx parameters.
4. With optimum values assigned to the DIGFLx
parameters, calculate the DFTHRH parameter 
value by converting the weight value recorded 
in Step 2 to display divisions:
threshold_weight_value / DSPDIV
In the example in Step 2, with a threshold 
weight value of 50 lb and a display division 
value of 5lb: 
50 / 5lb = 10DD.
DFTHRH should
be set to 10DD for this example.
5. Finally, set the DFSENS parameter high
enough to ignore transient peaks. Longer 
transients (typically caused by lower vibration 
frequencies) will cause more consecutive 
out-of-band readings, so DFSENS should be 
set higher to counter low frequency transients.
Reconfigure as necessary to find the lowest 
effective value for the DFSENS parameter.
7.8
Analog Output Calibration
The following calibration procedure requires a multimeter to measure voltage or current output from the analog 
output module. If the option is not already installed, see Section 2.3.5 on page 8.
XXXXXXX
XXXXXXX
ALGOUT
DIGIN
SETPNT
XXXXXXX
PROGRM
PFORMT
SERIAL
CALIBR
XXXXXXX
CONFIG
FORMAT
SOURCE
GROSS
0%
20%
OFFSET
ERRACT
FULLSC
HOLD
000000
number
MIN
10000
number
MAX
TWZERO
NET
ZEROSC
VERS
MINNEG
OFF
ON
MAXNEG
OFF
ON
Note
The analog output must be calibrated after the indicator itself has been configured (Section 3.0) and 
calibrated (Section 4.0).
Figure 7-5. Analog Output Menu
1. Enter setup mode and go to the ALGOUT
menu (see Figure 7-5).
•
Set OFFSET to 0% for 0–10 V output, 
20% for 4–20 mA output
•
Set MIN to lowest weight value to be 
tracked by the analog output
•
Set MAX to highest weight value to be 
tracked by the analog output
2. Connect multimeter to analog output:
•
For voltage output, connect voltmeter 
leads to pins three and four
•
For current output, connect ammeter leads 
to pins one and two
3. Adjust zero calibration: Scroll to the
TWZERO parameter. Check voltage or current 
reading on multimeter. Press and hold or 
to adjust the zero value up or down.
4. Adjust span calibration: Scroll to the TWSPAN
parameter. Check voltage or current reading on 
multimeter. Press and hold or to adjust the 
span value up or down.
5. Final zero calibration: Return to the TWZERO
parameter and verify that the zero calibration 
has not drifted. Press and hold or to 
re-adjust the zero value as required.
6. Return to normal mode. Analog output
function can be verified using test weights.
