26 glazing – Oldcastle BuildingEnvelope Reliance-TC User Manual
Page 26
GLAZING
R E L I A N C E - T C C U R T A I N W A L L I N S T A L L A T I O N M A N U A L
TM
Glazing Instructions
Location of Temporary
3" typ.
3" typ.
Glazing Retainers for Type II
SSG MULLION
FIGURE 24
FIGURE 23
MAY 2013
26
Phone: 1-866-OLDCASTLE (653-2278)
Web Address: www.oldcastlebe.com
3.8 When glazing Type II, set glass in opening, make sure that glass bite is equal on all sides. CAUTION: BE
certain that glass is placed firmly against interior gasket to ensure a proper seal and to avoid binding
of the glass on the setting block.
3.9 Temporarily hold glass in the opening with WW-333 temporary glazing retainers & FS-325 screw. Use
SPW-PP-3 retainer for SSG verticals. Torque the FS-325 screw to 60 in-lbs.
· WW-333 temporary glazing retainers must be applied at each glass edge 3" from the corner (minimum of 8
per lite). Glass edges greater than 4' in length but less than 8' require an additional retainer at the glass
mid-span.
· Retainers are intended for short term use only. Additional retainers may be required to withstand full design
wind load pressures.
· Full length pressure plates must be installed if severe weather or high wind loads are anticipated. SEE
FIGURE 23 & 24.
WW-333-01 temporary glazing retainer.
Locate at 3" from edge of glass. Additional
clips may be required based on field
conditions and glass size.
WW-370 zone plug
see FIGURE 10 for
sealant notes
FS-325
(1) per retainer
AW-127 setting chair w/
GP-116 setting block
(2) per D.L.O, locate at
1/4 points