Sill flashing installation, F) typical detail showing parts relationship, Step 2) – EFCO 960 Series User Manual
Page 44: Step 1), Fig. # 35, Fig. # 34, Fig. # 33
Anchor the sill flashing 24" O.C. and
best performance, locate the sill flashing splice 6" from vertical
If the elevation’s configuration consists of verticals through, for
cover the heads of all attachment
screws with sealant.
MINIMUM
Splice the sill flashing every 20’-0" as shown in Fig. # 35 below.
F-542 splice sleeve is supplied for use with the 4 13/16" back
member. Trim F-542 to the correct length for the particular
9982 - 3 3/4" TRIMMED
F960 WALL
9972 - 2 13/16" TRIMMED
Set the sill flashing splice in a bed
of sealant around the perimeter
of the splice.
3/8"
FIG. # 35
STEP 2)
SILL FLASHING NUMBER & LENGTH
9974 - 6 1/16" AS SUPPLIED
9668 - 5 5/16" TRIMMED
intermediates.
SEE
CHART
system depth being used.
FIG. # 34
formed sleeve
silicone to fill the joint.
Use backer rod and
JDA 6/2002
.050 aluminum
1" wide centered on splice.
1 1/2"
Bond breaker tape
6"
SECTION VII - SILL FLASHING INSTALLATION
"skinning", nonhardening type of
screws with sealant.
sealant (i.e., silicone).
Seal the ends of the sill flashing with a
Cover the heads of all attachment
Fill the vertical glazing pocket with sealant
to divert water onto the sill flashing.
door frame to masonry. Refer to Fig. # 33 & # 34 below.
Install the sill flashing continuously between the masonry jambs or
FIG. # 33
STEP 1)
and set it in a continuous bead
Shim the sill flashing until it is level
of sealant.
PAGE 42
Before the fastener is inserted,
force sealant into the hole for the
that the hole through the sill
sill perimeter fastener to ensure
flashing is sealed.