beautypg.com

Fail secure configuration (standard) – Detex DS-1481 User Manual

Page 4

background image

INSTRUCTIONS FOR CHANGING

FAIL SECURE TO FAIL SAFE

AND VICE VERSA:

To change the Fail Secure into a Fail Safe, open the mechanism

side (as shown on the right) by removing the mechanism cover

screws (3 places) and the cover. Lift the solenoid and gently pull off the

solenoid plunger. Replace the BLUE colored spring with the RED colored

spring. Pull off the actuator cam, and flip it to use the cam profile for Fail

Safe (the side without an “X” mark). Before closing the unit, make sure that

the wires are properly seated on the wire channel (see figure on right).

Save the BLUE colored spring for future use.

For changing from Fail Safe to Fail Secure, just reverse the above

procedure.

Turn the actuator cam over

to utilize the Fail Safe

side of the cam profile.

Use the BLUE colored

solenoid spring.

You should have

the “X” mark

on top of the

actuator cam.

Fail Secure

Configuration

(Standard)

Use the RED colored

solenoid spring.

You should NOT

see the “X”

on top of the

actuator cam.

DO NOT OPEN

THIS SIDE.

Seat wires properly in

the housing channel so

the cover will seat flat.

Fail Safe

Configuration

TROUBLESHOOTING THE COMPLETED INSTALLATION

SYMPTOM: Electric release is not actuating:

1. Verify proper voltage is present AT STRIKE. If voltage

is present: the strike may have been affected during

the installation, or dirt or debris may be preventing

proper operation. Inspect electric release and clean.

DO NOT LUBRICATE SOLENOID.

2. If voltage IS NOT present:

Verify Circuit breaker is on

Verify voltage at the transformer/power supply output.

Verify that there are no additional, external switches or

devices which may be interrupting your circuit.

Check for damaged wiring or bad wire splices.

SYMPTOM: Door will not open but strike is working

• Check for other locks on door

• Check for proper lock-latch engagement

• Check for excessive back pressure on door release

latch by following these steps:

Push the door from the outside to try and relieve

the bolt to latch pressure and actuate the strike.

While unlatched swing the door open. If the door

opens, then the bolt may be applying

pressure to the latch. Adjust the position

to relieve the pressure.

Possible remedies include:

• Re-adjust (or install) a door closer

• Remove door silencers

• Correct excessive door warpage

• Re-center electric release in jamb

• Remove or trim weather stripping around the door

4