Stardance direct vent - rear vent gas heaters, Selkirk direct-temp metalbestos direct vent system – Vermont Casting SDDVRBS User Manual

Page 22

background image

22

Stardance Direct Vent - Rear Vent Gas Heaters

20012950

Selkirk Direct-Temp Metalbestos Direct

Vent System

Installation Instructions
1. Determine whether the length of pipe fits the appli-

ance outlet by attempting to engage the parts. If the
parts engage smoothly, proceed to Step 2. If ob-
structions, interference or loose fit is noted, contact
the appliance manufacturer or Selkirk Metalbestos
with the dimensions of the appliance outlet.

2. Slide the length of pipe over the appliance outlet a

minimum of 1¹⁄₂” and screw to the appliance outlet
collar using a minimum of two (2) #8 x 1/4” sheet
metal screws.

Appliance Adapter (AAV)
The appliance adapter (AAV) adapts DIRECT-TEMP to
most direct vent appliances incorporating outlet collars
configured to receive most common 4” (ID) 6⁵⁄₈” (OD) or
5” (ID) by 8” (OD) “Twist Lock” Style, direct vent sys-
tems.
The adapter incorporates two (2) indentations on the
outer wall of the inlet end, which are designed to “Twist
Lock” into place upon attachment to the appliance
outlet. Align the adapter indentations with the entry
slots of the appliance outlet and slide together. Turn the
adapter clockwise approximately one-quarter turn to
lock in place. The outlet end of the adapter is standard
DIRECT-TEMP construction.

Framing Dimension Table 1

Model DT Ceiling Support (CS) Cathedral Ceiling Wall Thimble

Diameter

Firestop (FS)

Support CCS)

(WT)

4”

8¹⁄₄” x 8¹⁄₄”

10⁵⁄₈” x 10⁵⁄₈”

8¹⁄₄” x 8¹⁄₄”

5”

10¹⁄₈” x 10¹⁄₈”

14¹⁄₂” x 14¹⁄₂”

10¹⁄₈” x 10¹⁄₈”

Use of Sealant
It is not required to apply or use sealant on the inner
liner of DIRECT-TEMP. For outer wall joint sealing
considerations, follow appliance manufacturer recom-
mendations.
Joint Connection:
The pipe and elbows are assembled by inserting the
outlet (male) end of a length of pipe or elbow into the in-
let (female) end of an adjacent length of pipe or elbow.
Make sure the outlet end is fully seated within the inlet
end of the adjoining section and the gasket, located on
the inner liner of the inlet section is fully enclosed by the
inner liner of the outlet of the adjoining section. Push
in the Lock Tab such that it becomes seated within the
inward groove of the adjoining section. This locks the
joint in place. (Fig. 36)
Supporting DIRECT-TEMP: Vertical Support
Vertical installations can be supported by two methods:
Ceiling Support (CS) (used in flat ceiling installation)
comes with a support plate and a support collar. Install

�����
������������
����

Gasket

Lock Tab

Inlet End

Outlet End

ST922

To Termination

To Appliance

Fig. 36 Joint connection.

it by screwing the support plate to the top of the prop-
erly framed ceiling joist opening, using screws provided.
A round trim plate (TP) is attached to the ceiling, using
screws, to provide a finished appearance once in-
stalled. (Fig. 37)
The Cathedral Ceiling Support (CCS) may be used in
pitched or flat ceiling installations and comes with a
support collar and a decorative two part square trim
plate. Install by inserting the support box down through
the framed joist opening (end with round hole first) in
the ceiling using tin snips, cut the corners of the open
end of the box such that the sides can be folded down
over the top of the joist framing members. Nail the
folded sides to the top of the framing. (Fig. 38)

�����
�������
����������������
����

Ceiling Support
Plate

Ceiling Support
Collar

Trim Plate

ST923

Fig. 37 Ceiling support.

�����
�������������������
����

Two Part Square
Trim Plate

Support Box

Support Box Collar

ST926

Fig. 38 Support box.