beautypg.com

Stardance direct vent - rear vent gas heaters, Vertical (through the roof) vent assembly, Vertical through existing chimney – Vermont Casting SDDVRBS User Manual

Page 19: Fireplace vent termination clearances

background image

19

Stardance Direct Vent - Rear Vent Gas Heaters

20012950

Vertical (Through the Roof)

Vent Assembly

NOTE: All vertically terminated installations must,
where specified, use the restrictor plate, to com-
ply with Vertical Termination Window (Fig. 8, Page
8),
included in the hardware bag. The plate must be
installed as directed on Page 8, Figure 8.

Make certain the vent system conforms to all other
requirements for vertical termination as specified on
Page 9.

This installation will require you to first determine the
roof pitch and use the appropriate vent components.
Refer to Page 10, Figure 11.

1. Locate the final position of the stove, observing all

clearances for both the vent and the stove.

2. Plumb to the center of the inner (4”) flue collar from

the ceiling above, and mark that location.

3. Cut the opening: (Page 17, Fig. 23)
9³⁄₈” x 9³⁄₈” (240 x 240mm)
4. Plumb any additional opening through the roof or

other construction that may be needed. In all cases,
the opening must provide a minimum of 1” (25mm)
clearance to the vent pipe.

5. Place the stove in its final position.
6. Install firestop(s) #7DVFS and Attic Insulation Shield

#7DVAIS as needed. (Fig. 31) If there is a room
above ceiling level, a firestop must be installed on
both the bottom and top sides of the ceiling joists.
If an attic is above ceiling level, an attic insulation
shield must be installed.

ST222

vent thru ceiling

12/99

#7DVAIS

Attic Insulation

Shield

#7DVFS

Firestop in

Upper Floor

#7DVFS

Firestop in

Ceiling

Use Four
8d Nails

ST222

Fig. 31 Install firestops and attic insulation shield.

ST221

vent thru roof

12/99

Storm

Collar

Sealant

Upper edge

of flange goes

under upper

shingles

Flashing

#7DVSKV (A,

B, or F) Roof

Support

Use three #5

sheet metal

screws at

each joint

ST221

Fig. 32 Roof support and flashing.

7. Install the appropriate roof support and flashing,

making certain that the upper flange of the flashing
base is below the shingles. (Fig. 32)

8. Install appropriate pipe sections until the vent run

reaches above the flashing. The enlarged ends of
the vent sections always face downward.

9. Install the storm collar and seal around the joints. (Fig.

32)

10. Add additional vent lengths to achieve the proper

overall height.

11. Install termination cap.

Vertical Through Existing Chimney

The heater must be vented to the outdoors through an
existing masonry or prefabricated fireplace chimney
system through the roof.
The heater is approved to be vented to the outdoors
through any solid-fuel fireplace chimney that has been
constructed or installed in accordance with the na-
tional, Provincial/State and local building codes and is
constructed of noncombustible materials. For Venting
Requirements, refer to Page 10. Refer to Venting Com-
ponents on Pages 12 & 13.

Fireplace Vent Termination Clearances

Observe the chimney-top vent termination clearances
specified in the instructions provided with those compo-
nents. Some considerations are:

Obstructions or impediments to venting.

Nearby combustible materials that could come into
contact with combustion exhaust gases.

Other nearby openings within 9” (230 mm) through
which exhaust gas could reenter the building.