Rough-in Wiring

1. Branch circuits for the heaters shall be enclosed in 1” rigid

conduit for 05A heaters, or 1-1/4” rigid conduit for 07A
heaters.

2. Run branch circuit of proper voltage and wire size, in rigid

conduit, to location of left or right junction box as indicated
on heater wiring diagram. Wire entry to heater is through
either end pedestal.

Note When pedestal is not used for wire entry, pedestal base
must be covered with cover plate (supplied with pedestal). See
Figure 2.

3. When installing heaters on existing floors, the threaded end

of the rigid conduit must extend 7/8” to 1” above finished
concrete. Conduit must be threaded a minimum of 3/8”.

4. Basic heaters are prewired and can be connected to branch

circuit at either end. Heaters with controls are prewired for
connection to branch circuit at one end only (refer to heater
wiring diagram), however, heater can be wired from opposite
end by running wires through heater wireway.

5. If it is necessary to run wires through the heater wire way,

use Table B to size the field installed wiring.

6. The factory installed wires in the heater wireway can be

loaded up to 35 amps in 05A units and up to 45 amps in 07A
units. Refer to Table C and D for maximum length of heater
run when the heaters are connected in parallel.

Thermostat

24 amps @ 120-240 VAC
22 amps @ 277 VAC
Pilot duty– 125 VAC (all voltages)

Transformer relay

05A units:

22 amps @ 120-240 VAC
19 amps @ 277 VAC

07A Units:

25 AMPS @ 120-240 VAC
22 AMPS @ 277 VAC

Power relay

25 amps @ 120-277 VAC- see wiring dia-
gram on heater

Disconnect switch

20 amps @ 120-277 VAC

7. Standard 75˚C wiring must be used in junction boxes,

wire-

way and blank sections.

Room Layout

Refer to heating plans for exact room arrangements of heaters
(with or without thermostat and/or relays and/or switches and
accessories.)

Mounting Height

Refer to Figure 1a. for typical mounting of heaters and pedestals
imbedded in floor; refer to Figure 1b. for surface-mounted
heaters and pedestals.

Note: Up to 3/4” thick floor covering, such as carpet, tiles,
linoleum, etc., may be installed around and under the heater.

IF THE FACTORY INSTALLED WIRES IN THE WIREWAY
ARE USED TO CONNECT THE BUILT-IN CONTROLS, LIMIT
THE MAXIMUM CURRENT TO THE VALUES LISTED

3

Maximum allowable current

Copper

Maximum no.

wire size

of wires

Up to 3

4 to 6

7 thru 9

75º C

in wireway

Conductors

Conductors

Conductors

No. 12 AWG

9

11.5 amps

9.3 amps

8.1 amps

No. 10 AWG

8

17.4 amps

14.0 amps

12.1 amps

No. 8 AWG

4

24.0 amps

21.0 amps

Table B. Sizing Field Installed Wiring

Watts/Ft. of

Maximum allowable length of heater run (feet)

the heaters

120 Volts

208 Volts

240 Volts

277 Volts

125

33

58

67

77

188

22

38

44

51

250

16

29

33

38

Table C. Maximum Length of Heater Run
(05A-1Ø)

Note: For mix of watt densities, calculate amp draw. Do not
exceed values indicated in step 6 above.

TABLE D. Maximum Length of Heater Run
(07A - 1Ø and 3Ø)

Watts/Ft. of

Maximum Allowable Length of Heater Run (Feet)

the Heaters 208 Volts

208 Volts

240 Volts

240 Volts

277 Volts

1Ш`

125

74

-

86

-

99

188

49

-

57

-

66

250

37

-

43

-

49

376

24

-

28

-

33

500

18

-

21

-

24

564

16

27

19

32

22

625

14

24

17

29

19

750

12

20

14

24

16

Heater Capacity

(Watts.Ft. Heater Length)

125, 188 and 250 Watts/Ft.

376, 500, 564, 625 and 750

Watts/Ft.

Heater

Dimension “A”

(Minimum Mounting

Height Above Floor)

1-3/4”

3”

Pedestal

Dimension “B”

(Minimum Height

Above Floor)

2”

3-1/4”

Leveling

Nut

Locknut (Do

Not Loosen

Or Remove)

Floor

Line

Pedestal

Locknut

Welded
Bracket

Heater

2-7/8” (5” Heaters)
4-1/8” (7” Heaters)

3/8”

Figure 1a. Pedestal Imbedded in Floor

Welded
Bracket

Locknut

Leveling

Nut

Locknut (Do

Not Loosen

Or Remove)

Floor

Line

A

A

B

Heater

Pedestal

Base Mounting

Holes - 1/4” DIa.

(Suitable

Fasteners By

Others)

Rigid

Conduit

Figure 1b. Surface-Mounted Pedestal

Heater Catalog Number

Height Above Floor (Dim. “A)

Min.

Max.

05A

2-5/8”

3-3/8”

07A

3-7/8”

4-5/8”