beautypg.com

Appendix a — wshp open screen configuration – Carrier AQUAZONE 50RTP03-20 User Manual

Page 50

background image

50

APPENDIX A — WSHP OPEN SCREEN CONFIGURATION

LEGEND

SCREEN NAME

PASSWORD

LEVEL

POINT NAME

EDITABLE

RANGE

DEFAULT

NOTES

Equipment

Status

No Password

Required

Operating Mode

Off, Fan Only, Economize,

Cooling, Heating, Cont Fan,

Test, Start Delay, Dehumidify

Displays unit operating mode

SPT

F

Displays SPT

SAT

F

Displays SAT

Condenser Leaving

Temperature

F

Displays leaving condenser

water temperature

Condenser Entering

Temperature

F

Displays entering condenser

water temperature (Value

will not update when compressor

is operating)

Fan

Off/Low Speed/

Medium Speed

High Speed/On

Displays fan speed status

Compressor Capacity

0 - 100%

Displays compressor capacity

Damper Position

0 - 100%

Displays current damper position
(Viewable only if Ventilation DMP

Type = 2 position or DCV)

H

2

O Economizer

0 - 100%

Displays position of economizer valve

Auxiliary Heat

0 - 100%

Displays position of auxiliary

reheat valve (Viewable only if Leaving

Air Auxiliary Heat Type = 2 position,

1 stage Elect or Modulating)

Space RH

0 - 100%

Displays space RH% (Viewable only if

Humidity Sensor = Installed)

Dehumidification

Inactive/Active

Displays if dehumidification is active

(Viewable only if Factory

Dehumidification Reheat = Installed)

IAQ CO

2

0 - 9999 ppm

Displays the space CO

2

level

Alarm Status

No Password

Required

SPT Alarm Status

Normal/Alarm

Displays current space

temperature condition

Alarming SPT

F

Displays the SPT that

exceeded the alarm limit (when SPT

alarm above is in Alarm)

SPT Alarm Limit

F

Displays the SPT alarm limit that was

exceeded; causing the alarm condition

(when SPT alarm above is in Alarm)

SPT Sensor Alarm

Status

Normal/Alarm

Displays the status of the Rnet

SPT sensor - ALARM is displayed

should the sensor fail to communicate

with the control module

IAQ Alarm Status

Normal/Alarm

Current IAQ/ventilation condition

Compressor Alarm

Status

Normal/Alarm

Current compressor condition

SAT Alarm Status

Normal/Alarm

Current SAT condition

Condensate Overflow

Alarm Status

Normal/Alarm

Current status of the condensate

drain (overflow switch)

Condenser Water Tem-

perature Alarm Status

Normal/Alarm

Current status of the

condenser water

Filter Alarm Status

Normal/Alarm

Current filter condition

Space RH Alarm Status

Normal/Alarm

Current space RH condition

OAT Alarm Status

Normal/Alarm

Current status of the OAT

broadcast function

Airside Linkage Status

Normal/Alarm

Current linkage status if enabled

Condenser Water

Linkage

Normal/Alarm

Current linkage status if enabled

Sensor

Calibration

Admin Password

level access only

SAT

F

Display SAT

SAT Offset

X

-9.9 - 10.0 F

0 F

Used to correct sensor reading

Leaving Condenser

Water Temperature

F

Displays Leaving Condenser

Water Temperature

Leaving CW Offset

X

-9.9 - 10.0 F

0 F

Used to correct sensor reading

Rnet Sensor
Temperature

F

Displays SPT

Rnet Offset

X

-9.9 - 10.0 F

0 F

Used to correct sensor reading

RH

%

Displays Space RH value

RH Sensor Offset

X

-15% - 15%

0 %

Used to correct sensor reading


BAS — Building Automation System
DCV — Demand Controlled Ventilation

ECM — Electronically Commutated Motor

IAQ

Indoor Air Quality

OAT

Outdoor Air Temperature

RH

Relative Humidity

SAT

Supply Air Temperature

SPT

Space Temperature

TPI

Third Party Integration