beautypg.com

Carrier AQUAZONE 50RTP03-20 User Manual

Page 2

background image

2

Follow all safety codes. Wear safety glasses and work

gloves. Use quenching cloth for brazing operations. Have fire

extinguisher available. Read these instructions thoroughly and

follow all warnings or cautions attached to the unit. Consult

local building codes and the National Electrical Code (NEC)

for special installation requirements.

Understand the signal words — DANGER, WARNING,

and CAUTION. DANGER identifies the most serious hazards

which will result in severe personal injury or death. WARN-

ING signifies hazards that could result in personal injury or

death. CAUTION is used to identify unsafe practices, which

would result in minor personal injury or product and property

damage.

Recognize safety information. This is the safety-alert

symbol (

). When you see this symbol on the unit and in

instructions or manuals, be alert to the potential for personal

injury.

GENERAL

This Installation and Start-Up Instructions literature is for

Aquazone™ rooftop water source heat pump systems.

Rooftop water source heat pumps (WSHP) are single-pack-

age outdoor units with electronic controls designed for year-

round cooling and heating.

INSTALLATION

Step 1 — Check Jobsite —

Installation, operation and

maintenance instructions are provided with each unit. Before

unit start-up, read all manuals and become familiar with the

unit and its operation. Thoroughly check out the system before

operation. Complete the inspections and instructions listed

below to prepare a unit for installation. See Table 1 for unit

physical data.

Step 2 — Check Unit —

Upon receipt of shipment at

the jobsite, carefully check the shipment against the bill of

lading. Make sure all units have been received. Inspect the car-

ton or crating of each unit, and inspect each unit for damage.

Ensure the shipping company makes proper notation of any

shortages or damage on all copies of the freight bill. Concealed

damage not discovered during unloading must be reported to

the shipping company within 15 days of receipt of shipment.
NOTE: It is the responsibility of the purchaser to file all

necessary claims with the shipping company.

1. Verify unit is correct model for entering water tempera-

ture of job.

2. Be sure to provide freeze protection for piping, as re-

quired. Well water applications are especially susceptible

to freezing.

3. Be sure the installation location is isolated from sleeping

areas, private offices and other acoustically sensitive

spaces.

4. Check local codes to be sure a secondary drain pan is not

required under the unit.

5. Be sure unit is mounted at a height sufficient to provide

an adequate slope of the condensate lines. If an appropri-

ate slope cannot be achieved, a field-supplied condensate

pump may be required.

6. Provide sufficient space for duct connection.
7. Provide adequate clearance for filter replacement and

drain pan cleaning. Do not allow piping, conduit, etc. to

block filter access.

8. Provide sufficient access to allow maintenance and

servicing of the fan and fan motor, compressor and coils.

9. Provide an unobstructed path to the unit. Space should be

sufficient to allow removal of unit if necessary.

10. Provide ready access to water valves and fittings, and

screwdriver access to unit side panels, discharge collar,

and all electrical connections.

11. Where access to side panels is limited, pre-removal of the

control box side mounting screws may be necessary for

future servicing.

STORAGE — If the equipment is not installed immediately

upon its arrival at the jobsite, it should be left in its shipping

carton and stored in a clean, dry area of the building or in a

warehouse. Units must be stored in an upright position at all

times. If unit stacking is necessary, stack 50RTP03-10 units a

maximum of 2 high. Do not stack units larger than 50RTP10.

Do not remove any equipment from its shipping package until

it is needed.
PROTECTION — Once the units are properly positioned on

the jobsite, they must be covered with either a shipping carton,

vinyl film, or an equivalent protective covering. Open ends of

pipes stored on the jobsite must be capped. This precaution is

especially important in areas where painting, plastering, or

spraying of fireproof material, etc. is not yet complete. Foreign

material that is allowed to accumulate within the units can pre-

vent proper start-up and necessitate costly clean-up operations.

Before installing any of the system components, be sure to

examine each pipe, fitting, and valve, and remove any dirt or

foreign material found in or on these components.

WARNING

Electrical shock can cause personal injury and death. Shut

off all power to this equipment during installation. There

may be more than one disconnect switch. Tag all discon-

nect locations to alert others not to restore power until work

is completed.

CAUTION

This system uses R-410A, which has higher pressures than

R-22 and other refrigerants. No other refrigerant may be

used in this system. Suction tubing design pressure is

445 psig (3068 kPa) and liquid tubing design pressure

is 656 psig (4522 kPa). Failure to use gage set, hoses,

and recovery systems designed to handle R-410A

refrigerant may result in personal injury and equipment

damage. If unsure about equipment, consult the equipment

manufacturer.

IMPORTANT: The installation of water source heat pump

units and all associated components, parts, and accessories

which make up the installation shall be in accordance with

the regulations of ALL authorities having jurisdiction and

MUST conform to all applicable codes. It is the responsi-

bility of the installing contractor to determine and comply

with ALL applicable codes and regulations.

CAUTION

To avoid equipment damage, do not use these units as a

source of heating or cooling during the construction pro-

cess. The mechanical components and filters used in these

units quickly becomes clogged with construction dirt and

debris which may cause system damage.