35

PRE-START-UP

System Checkout —

When the installation is complete

and the system is cleaned and flushed, follow the System

Checkout procedure outlined below.

1. Voltage: Ensure that the voltage is within the utilization

range specifications of the unit compressor and fan motor.

2. System Water Temperature: Ensure that the system

water temperature is within an acceptable range to facili-

tate start-up. (When conducting this check, also verify

proper heating and cooling set points.)

3. System Water pH: Verify system water acidity

(pH = 7.5 or 8.5). Proper pH promotes the longevity of

hoses and heat exchangers.

4. System Flushing: Properly clean and flush the system

periodically. Ensure that all supply and return hoses are

connected end-to-end to facilitate system flushing and

prevent fouling of the heat exchanger by system water.

Water used in the system must be potable and should not

contain dirt, piping slag, and chemical cleaning agents.

5. Closed-Type Cooling Tower or Open Tower with Heat

Exchanger: Check equipment for proper temperature set

points and operation.

6. Verify Balanced Water Flow Rate to Heat Pump.
7. Standby Pump: Verify that the standby pump is properly

installed and in operating condition.

8. Access Panels: Assure that all access panels in the filter

and fan section are securely closed.

9. Air Dampers: Assure that all air dampers are properly

set.

10. System Controls: To ensure that no catastrophic system

failures occur, verify that system controls are functioning

and that the sequencing is correct.

11. Freeze Protection for Water System: Verify that freeze

protection is provided for the building loop water system

when outdoor design conditions require it. Inadequate

freeze protection can lead to expensive tower and system

piping repairs.

12. System Water Loop: Verify that all air is bled from the

system. Air in the system impedes unit operation and

causes corrosion in the system piping.

13. Unit Filters: To avoid system damage, check that the unit

filter is clean.

14. Unit Fans: Manually rotate fans to assure free rotation.

Ensure that fans are properly secured to the fan shaft. Do

not oil fan motors on start-up since they are lubricated at

the factory.

15. System Control Center: Examine the system control

and alarm panel for proper installation and operation to

ensure control of the temperature set-points for operation

of the system’s heat rejector and boiler (when used).

16. Miscellaneous: Note any questionable aspects of the

installation.

17. Air Coil: To obtain maximum performance, the air coil

should be cleaned before starting the unit. A ten percent

solution of dishwasher detergent and water is recom-

mended for both sides of the coil. Rinse thoroughly with

water.

FIELD SELECTABLE INPUTS

Jumpers and DIP (dual in-line package) switches on the

control board are used to customize unit operation and can be

configured in the field.

Complete C Control Jumper Settings (See
Fig. 6 and 7)

WATER COIL FREEZE PROTECTION (FP1) LIMIT

SETTING — Select jumper 3, (JW3-FP1 Low Temp) to

choose FP1 limit of 10 F or 30 F. To select 30 F as the limit,

DO NOT clip the jumper. To select 10 F as the limit, clip the

jumper.
AIR COIL FREEZE PROTECTION (FP2) LIMIT SET-

TING — Select jumper 2 (JW2-FP2 Low Temp) to choose

FP2 limit of 10 F or 30 F. To select 30 F as the limit, DO NOT

clip the jumper. To select 10 F as the limit, clip the jumper.
ALARM RELAY SETTING — Select jumper 1 (JW1-AL2

Dry) for connecting alarm relay terminal (AL2) to 24 vac (R)

or to remain as a dry contact (no connection). To connect AL2

to R, do not clip the jumper. To set as dry contact, clip the

jumper.

Complete C Control DIP Switches —

The Com-

plete C control has 1 DIP switch block with two switches. See

Fig. 6 and 7.
PERFORMANCE MONITOR (PM) — DIP switch 1 will

enable or disable this feature. To enable the PM, set the switch

to ON. To disable the PM, set the switch to OFF.
STAGE 2 — DIP switch 2 will enable or disable compressor

delay. Set DIP switch to OFF for stage 2 in which the compres-

sor will have a 3-second delay before energizing.
NOTE: The alarm relay will not cycle during Test mode if

switch is set to OFF, stage 2.

Deluxe D Control Jumper Settings (See Fig. 9
and 10)

WATER COIL FREEZE PROTECTION (FP1) LIMIT

SETTING — Select jumper 3, (JW3-FP1 Low Temp) to

choose FP1 limit of 10 F or 30 F. To select 30 F as the limit, DO

NOT clip the jumper. To select 10 F as the limit, clip the jumper.
AIR COIL FREEZE PROTECTION (FP2) LIMIT SET-

TING — Select jumper 2 (JW2-FP2 Low Temp) to choose

FP2 limit of 10 F or 30 F. To select 30 F as the limit, DO NOT

clip the jumper. To select 10 F as the limit (for anti-freeze sys-

tems), clip the jumper.
ALARM RELAY SETTING — Select jumper 4 (JW4-AL2

Dry) for connecting alarm relay terminal (AL2) to 24 vac (R)

or to remain as a dry contact (no connection). To connect AL2

to R, do not clip the jumper. To set as dry contact, clip the

jumper.
LOW PRESSURE SETTING — The Deluxe D control can

be configured for Low Pressure Setting (LP). Select jumper 1

(JW1-LP Norm Open) for choosing between low pressure in-

put normally opened or closed. To configure for normally

closed operation, do not clip the jumper. To configure for nor-

mally open operation, clip the jumper.

Deluxe D Control DIP Switches —

The Deluxe D

control has 2 DIP switch blocks. Each DIP switch block has 8

switches and is labeled either S1 or S2 on the circuit board.
DIP SWITCH BLOCK 1 (S1) — This set of switches offers

the following options for Deluxe D control configuration:
Performance Monitor (PM) — Set switch 1 to enable or dis-

able performance monitor. To enable the PM, set the switch to

ON. To disable the PM, set the switch to OFF.
Compressor Relay Staging Operation — Switch 2 will en-

able or disable compressor relay staging operation. The com-

pressor relay can be set to turn on with stage 1 or stage 2 call

IMPORTANT: Jumpers and DIP switches should only

be clipped when power to control board has been turned

off.