10

Example: Supply voltage is 460-3-60.

AB = 452 volts

BC = 464 volts

AC = 455 volts

Determine maximum deviation from average voltage:
(AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v

(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance.

= 1.53%

This amount of phase imbalance is satisfactory as it is

below the maximum allowable 2%.

Operation on improper line voltage or excessive phase

imbalance constitutes abuse and may cause damage to electri-

cal components.
NOTE: If more than 2% voltage imbalance is present, contact

local electric utility.
208-VOLT OPERATION — All 208-230 volt units are factory

wired for 208 volts. The transformers may be switched to

230-volt operation (as illustrated on the wiring diagram) by

switching the red (208 volt) wire with the orange (230 volt)

wire at the L1 terminal.
BLOWER SELECTION — All water source heat pumps are

factory set with the appropriate motor and sheave combination

to achieve the desired airflow performance. Performance is

selected by matching the desired performance with the appro-

priate region in Tables 4-12.
NOTE: Factory-installed sheaves are field adjustable. Refer to

Tables 4-12 for adjustment points.

Table 3 — Electrical Data

Average Voltage =

452 + 464 + 455

3

=

1371

3

= 457

% Voltage Imbalance = 100 x

7

457

50RTP

UNIT SIZE

VOLTAGE

CODE

VOLTAGE

(V-Ph-Hz)

MIN/MAX

VOLTAGE

BLOWER

OPTION

COMPRESSOR

MOTOR

TOTAL

UNIT

FLA

MCA

MAX

FUSE/

HACR

Qty

RLA

LRA

Qty

FLA

Hp

03

5

208-3-60

197/254

A,B,C

1

10.4

73.0

1

4.0

1.0

14.4

17.0

25

6

460-3-60

414/506

A,B,C

1

5.8

38.0

1

2.0

1.0

7.8

9.3

15

1

575-3-60

518/633

A,B,C

1

3.8

36.5

1

1.4

1.0

5.2

6.2

15

04

5

208-3-60

197/254

A,B,C

1

13.7

83.1

1

4.0

1.0

17.7

21.1

35

D,E

1

13.7

83.1

1

5.0

1.5

18.7

22.1

35

6

460-3-60

414/506

A,B,C

1

6.2

41.0

1

2.0

1.0

8.2

9.8

15

D,E

1

6.2

41.0

1

2.4

1.5

8.6

10.1

15

1

575-3-60

518/633

A,B,C

1

4.8

33.0

1

1.4

1.0

6.2

7.4

15

D,E

1

4.8

33.0

1

1.9

1.5

6.7

7.9

15

05

5

208-3-60

197/254

A,B,C

1

15.6

110.0

1

4.0

1.0

19.6

23.5

40

D,E

1

15.6

110.0

1

5.0

1.5

20.6

24.5

40

6

460-3-60

414/506

A,B,C

1

7.8

52.0

1

2.0

1.0

9.8

11.8

15

D,E

1

7.8

52.0

1

2.4

1.5

10.2

12.2

15

1

575-3-60

518/633

A,B,C

1

5.8

38.9

1

1.4

1.0

7.2

8.7

15

D,E

1

5.8

38.9

1

1.9

1.5

7.7

9.2

15

06

5

208-3-60

197/254

A,B,C

1

20.5

155.0

1

5.0

1.5

25.5

30.6

50

E

1

20.5

155.0

1

6.2

2.0

26.7

31.8

50

6

460-3-60

414/506

A,B,C

1

9.6

75.0

1

2.4

1.5

12.0

14.4

20

E

1

9.6

75.0

1

3.1

2.0

12.7

15.1

20

1

575-3-60

518/633

A,B,C

1

7.6

54.0

1

1.9

1.5

9.5

11.4

15

E

1

7.6

54.0

1

2.3

2.0

9.9

11.8

15

08

5

208-3-60

197/254

A,B,C

2

13.7

83.1

1

6.2

2.0

33.6

37.0

50

E

2

13.7

83.1

1

9.2

3.0

36.6

40.0

50

6

460-3-60

414/506

A,B,C

2

6.2

41.0

1

3.1

2.0

15.5

17.0

20

E

2

6.2

41.0

1

4.3

3.0

16.7

18.3

20

1

575-3-60

518/633

A,B,C

2

4.8

33.0

1

2.3

2.0

11.9

13.1

15

E

2

4.8

33.0

1

3.4

3.0

13.0

14.2

15

10

5

208-3-60

197/254

A,B,C

2

15.6

110.0

1

9.2

3.0

40.4

44.3

60

E

2

15.6

110.0

1

14.1

5.0

45.3

49.2

60

6

460-3-60

414/506

A,B,C

2

7.8

52.0

1

4.3

3.0

19.9

21.9

25

E

2

7.8

52.0

1

7.0

5.0

22.6

24.6

30

1

575-3-60

518/633

A,B,C

2

5.8

38.9

1

3.4

3.0

15.0

16.5

20

E

2

5.8

38.9

1

5.2

5.0

16.8

18.3

20

12

5

208-3-60

197/254

A,B,C

2

20.5

155.0

1

9.2

3.0

50.2

55.3

80

D,E

2

20.5

155.0

1

14.1

5.0

55.1

60.2

80

6

460-3-60

414/506

A,B,C

2

9.6

75.0

1

4.3

3.0

23.5

25.9

35

D,E

2

9.6

75.0

1

7.0

5.0

26.2

28.6

35

1

575-3-60

518/633

A,B,C

2

7.6

54.0

1

3.4

3.0

18.6

20.5

25

D,E

2

7.6

54.0

1

5.2

5.0

20.4

22.3

25