39

e. Enter ON/OFF time, then press continue.
f. Press OK to apply and save to a particular day of

the week.

g. Continue to add the same or different schedule spe-

cific days of the week.
To add exceptions to the schedule:
i. Press Add softkey.
ii. Select exception type from following:

• Date

• Date Range

• Week-N-Day

• Calender Reference

9. Go back to Home Screen.

10. Remove BACview

6

cable from SPT sensor by reversing

the process in Step 1.

11. Perform system test.

Flow Regulation —

Flow regulation can be accom-

plished by two methods. Most water control valves have a flow

adjustment built into the valve. By measuring the pressure drop

through the unit heat exchanger, the flow rate can be deter-

mined. Adjust the water control valve until the flow of 1.5 to 2

gpm is achieved. Since the pressure constantly varies, two

pressure gages may be needed in some applications.

An alternative method is to install a flow control device.

These devices are typically an orifice of plastic material de-

signed to allow a specified flow rate that are mounted on the

outlet of the water control valve. Occasionally these valves

produce a velocity noise that can be reduced by applying some

back pressure. To accomplish this, slightly close the leaving

isolation valve of the well water setup.

System Cleaning and Flushing —

Cleaning and

flushing the unit is the single most important step to ensure

proper start-up and continued efficient operation of the system.

Follow the instructions below to properly clean and flush the

system:

1. Verify that electrical power to the units is disconnected.
2. Install the system with the supply hose connected directly

to the return riser valve. Use a single length of flexible

hose.

3. Open all air vents. Fill the system with water. Do not al-

low system to overflow. Bleed all air from the system.

Check the system for leaks and repair appropriately.

4. Verify that all strainers are in place. Start the pumps and

systematically check each vent to ensure that all air is

bled from the system.

5. Verify that makeup water is available. Adjust makeup

water appropriately to replace the air which was bled

from the system. Check and adjust the water/air level in

the expansion tank.

6. Set the boiler (when used) to raise the loop temperature to

approximately 85 F. Open a drain at the lowest point in

the system. Adjust the makeup water replacement rate to

equal the rate of bleed.

7. Refill the system and add trisodium phosphate in a pro-

portion of approximately one pound per 150 gallons of

water. Reset the boiler (when used) to raise the loop tem-

perature to about 100 F. Circulate the solution for a

minimum of eight to 24 hours. At the end of this period,

shut off the circulating pump and drain the solution. Re-

peat system cleaning if necessary.

8. When the cleaning process is complete, remove the short-

circuited hoses. Reconnect the hoses to the proper supply

and return the connections to each of the rooftop units.

Refill the system and bleed off all air.

9. Add antifreeze to the system in climates where ambient

temperature falls below freezing, using the proportion of

antifreeze shown in Table 17. The volume of antifreeze

required will vary based on outdoor design temperature.

10. Test the system pH with litmus paper. The system water

should be slightly alkaline ( pH 7.5 to 8.5). Add chemi-

cals as appropriate to maintain acidity levels.

11. When the system is successfully cleaned, flushed, refilled

and bled, check the main system panels, safety cutouts,

and alarms. Set the controls to properly maintain loop

temperatures.

NOTE: Carrier strongly recommends all piping connections,

both internal and external to the unit, be pressure tested by an

appropriate method prior to any finishing of the interior space

or before access to all connections is limited. Test pressure

may not exceed the maximum allowable pressure for the unit

and all components within the water system.

Carrier will not be responsible or liable for damages from

water leaks due to inadequate or lack of a pressurized leak test,

or damages caused by exceeding the maximum pressure rating

during installation.

Antifreeze —

In areas where entering loop temperatures

drop below 40 F or where piping will be routed through areas

subject to freezing, antifreeze is needed.

Alcohols and glycols are commonly used as antifreeze

agents. Freeze protection should be maintained to 15 F below

the lowest expected entering loop temperature. For example, if

the lowest expected entering loop temperature is 30 F, the leav-

ing loop temperature would be 22 to 25 F. Therefore, the freeze

protection should be at 15 F (30 F – 15 F = 15 F).

Calculate the total volume of fluid in the piping system. Use

the percentage by volume in Table 17 to determine the amount

of antifreeze to use. Antifreeze concentration should be

checked from a well mixed sample using a hydrometer to mea-

sure specific gravity.
FREEZE PROTECTION SELECTION — The 30 F FP1 fac-

tory setting (water) should be used to avoid freeze damage to

the unit.

Once antifreeze is selected, the JW3 jumper (FP1) should

be clipped on the control to select the low temperature (anti-

freeze 13 F) set point to avoid nuisance faults.

WARNING

Electrical shock can cause personal injury and death. Shut

off all power to this equipment during installation. There

may be more than one disconnect switch. Tag all discon-

nect locations to alert others not to restore power until

flushing is completed.

CAUTION

To avoid possible damage to piping systems constructed of

plastic piping, DO NOT allow loop temperature to exceed

115 F.

CAUTION

Do Not use “Stop-Leak” or any similar chemical agent in

this system. Addition of these chemicals to the loop water

will foul the system and will inhibit unit operation.

IMPORTANT: All alcohols should be pre-mixed and

pumped from a reservoir outside of the building or

introduced under water level to prevent fumes.