3 binary inputs, 4 outputs, 1 analog outputs – Dynalco SWT-2000 Speed Switch/Speed Transmitter User Manual
Page 9: Or i, Are considered to be faulty. i, 5…35ma i, Input resistance r, 2 k ω
Operating Instructions SWT-2000
DYNALCO
5
Sensor monitoring
3 sensor monitoring settings are available in the configuration software:
• No Sensor Monitoring
• Monitoring of supplied sensors (active Sensor Types)
[Also for 2 wire sensors that are supplied via the internal Pull-up resistor (1k
Ω)
Æ
Sensors drawing current outside of I
min
or I
max
are considered to be faulty.
I
min
= 0.5…35mA
I
max
= 0.5…35mA
• Monitoring of non powered sensors (passive Sensor Types)
[For 2 wire sensors such as electromagnetic sensors.]
Æ
The sensor is considered to be faulty if the line is broken.
Here the sensor impedance is dynamically measured.
Z < 60 k
Ω = OK
Z > 125 k
Ω = NOT OK
2.3 Binary Inputs
Number
2 Active Binary Inputs and 1 push button (FUNC – logic OR with Binary input B1)
Level
Logic 0 = 0V….+5V
Logic 1 = +15V….+36V
Isolation voltage
1500 V
RMS
Input resistance
R
min
= 8.2 k
Ω
2.4 Outputs
2.4.1 Analog Outputs
Number 2
Analog
outputs
Isolation voltage
1000 VDC
Output type
Current (selectable 0…20 / 4…20mA)
Load
Max. 500
Ω
Open circuit voltage
Max. 15V
Typical error curve
-1
-0.9
-0.8
-0.7
-0.6
-0.5
-0.4
-0.3
-0.2
-0.1
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
0.
00
E
+00
1.
00
E
-0
3
2.
00
E
-0
3
3.
00
E
-0
3
4.
00
E
-0
3
5.
00
E
-0
3
6.
00
E
-0
3
7.
00
E
-0
3
8.
00
E
-0
3
9.
00
E
-0
3
1.
00
E
-0
2
1.
10
E
-0
2
1.
20
E
-0
2
1.
30
E
-0
2
1.
40
E
-0
2
1.
50
E
-0
2
1.
60
E
-0
2
1.
70
E
-0
2
1.
80
E
-0
2
1.
90
E
-0
2
2.
00
E
-0
2
I (A)
M
e
as
u
re
m
en
t e
rro
r (
%
)
0.2 % (from measured value) + 2 LSB
CLASS 0.1 % (from End Value)