8 settings – Dynalco SWT-2000 Speed Switch/Speed Transmitter User Manual

Page 26

background image

Operating Instructions SWT-2000

DYNALCO


22

6.7.12 Copy Parameter Set


Go to , .

A Parameter set may only be copied from Parameter set A. The following Parameters will be copied:

- Machine factor 1 and 2

- Difference

- Math Function selection

- Upper and Lower Limits in System Limits

- System

Limit

inversion

- Inclusion of input in the logical combination

- Inclusion of Sensor alarm in the logical combination

- Relay / Open Collector assignment

- Relay / Open Collector latch mode

- Relay / Open Collector fail safe mode

- Analog output assignment

- 0..20mA

or

4..20mA

setting

- Start and End values

- Analog output time constant

6.7.13 Change-Over Delay


Go to , .

One change-over delay may be set for the delay in switching from Parameter set B to Parameter set A only.

Delay time:

0

… 2000 Seconds


Only integer values can be used for the change-over delay.

6.8 Settings

6.8.1 Ethernet Interface

Go to , .

No settings can be made. The PC- SWT-2000 connection is Peer to Peer
(PC to PC). SWT-2000’s cannot be connected to a network!

For technical data see Paragraph 2.5.1 Ethernet.

DHCP

Server

ON

/ OFF

TCP/IP

Adresse 192.168.1.127

TCP/IP Maske

255.255.255.0