beautypg.com

Dynalco SWT-2000 Speed Switch/Speed Transmitter User Manual

Page 20

background image

Operating Instructions SWT-2000

DYNALCO


16

6.7.2 Binary Input Configuration


To configure binary inputs go to , .

The following options are available for each binary input:

Logic level:

Active high

/ Active low

Function of binary input: Input for System Limit / Selection of Control (A/B) (C/D) / Reset latch

Logic level definition

Active High:

Logic 1 = binary input 15V …33V


Active Low:

Logic 1 = binary input 0V … 5V


Binary input for


System Limit input:

Binary input is a constituent part of System Limits.


Parameter set selection:

Binary inputs select the parameter set (PS), see Paragraph 7.3.2 Parameter sets A, B, C and D


Reset latch:

Binary input resets the relays and open collectors.

6.7.3 Set Measurement Interval


Go to , .

This time interval determines the period during which the speed, parameters, status and outputs are
recalculated and set accordingly.

Measurement time:

2ms

/ 5ms / 10ms / 20ms / 50ms /

100ms / 200ms / 500ms / 1s / 2s / 5s

6.7.4 Sensor Alarm


Go to , .

There are 3 sources of errors which may be OR

ed

together. Each error source may be included or excluded.


Static error sensor 1:

On / Off

Static error sensor 2:

On / Off

Dynamic error:

On / Off


Box checked = On, unchecked = Off
(see also Paragraph 6.7.1 Speed sensors).

Dynamic Error can only be used when 2 sensors are present. (see Paragraph 6.7.6 Dynamic Error).