Dynalco SWT-2000 Speed Switch/Speed Transmitter User Manual
Page 20
Operating Instructions SWT-2000
DYNALCO
16
6.7.2 Binary Input Configuration
To configure binary inputs go to
The following options are available for each binary input:
Logic level:
Active high
/ Active low
Function of binary input: Input for System Limit / Selection of Control (A/B) (C/D) / Reset latch
Logic level definition
Active High:
Logic 1 = binary input 15V …33V
Active Low:
Logic 1 = binary input 0V … 5V
Binary input for
System Limit input:
Binary input is a constituent part of System Limits.
Parameter set selection:
Binary inputs select the parameter set (PS), see Paragraph 7.3.2 Parameter sets A, B, C and D
Reset latch:
Binary input resets the relays and open collectors.
6.7.3 Set Measurement Interval
Go to
This time interval determines the period during which the speed, parameters, status and outputs are
recalculated and set accordingly.
Measurement time:
2ms
/ 5ms / 10ms / 20ms / 50ms /
100ms / 200ms / 500ms / 1s / 2s / 5s
6.7.4 Sensor Alarm
Go to
There are 3 sources of errors which may be OR
ed
together. Each error source may be included or excluded.
Static error sensor 1:
On / Off
Static error sensor 2:
On / Off
Dynamic error:
On / Off
Box checked = On, unchecked = Off
(see also Paragraph 6.7.1 Speed sensors).
Dynamic Error can only be used when 2 sensors are present. (see Paragraph 6.7.6 Dynamic Error).