Operating Instructions SWT-2000

DYNALCO


4

Input signal for adaptive
trigger min. 500mVpp
(+/-10%) 180mV

RMS

• Max. Voltage: 80V

RMS

(226V

pp

)

• DC-

decoupling

• The Trigger level automatically adapts itself to the input signal in the range

+250mV to +2V. The Adaptive Trigger improves the signal to noise immunity
e.g. where electromagnetic sensors are used.

M in. T rigger level: 500 mVpp +/-10% = 180 mV

RMS

+/-10% U min. = f(Frequency)

0.1

1.0

10.0

100.0

1000.0

0.

01

0.

1

1

10

100

1000

1

0000

10

0000

Freque ncy (Hz)

S

e

nsor

S

ig

n

a

l (

V

pp

)

O.K.

NOT O.K.

Sensor supply

• +14V +/- 0.5V, max. 35mA / Short circuit proof

• If the current limit has been activated, then the circuit needs to be

disconnected to reset the protection.


Typical voltage curve as a function of sensor current

Sensor voltage = f (Sensor current)

13.6

13.8

14.0

14.2

14.4

14.6

14.8

0

5

10

15

20

25

30

35

40

45

Sensor current (mA)

S

e

n

s

o

r vo

lt

ag

e (

V

)

Integral pull up resistor

1000

Ω to +14V (Only for 2 wire active e.g. NAMUR sensors)

Screen

Terminals are provided for each sensor cable screen (Sh1 and Sh2). These
terminals are internally connected to the sensor input / supply 0V.