Operating Instructions SWT-2000

DYNALCO


26

7.2.2 Signal Failure

Signal failure is defined as the sudden transition from an input frequency to no further recognisable pulses.
The frequency is then calculated as follows:

n

t

f

×

=

t

Measuremen

1

n: the number of measurement intervals without an input signal


The measured speed thereby follows an exponential function to the minimum frequency (0.025Hz) and then
falls to zero.

7.3 Functions

7.3.1 “FUNC” Push Button

The front panel “FUNC“ button is OR

ed

with binary input B1. Pushing this button executes the B1 function.

7.3.2 Parameter Sets A, B, C and D

The binary inputs must be used to change parameter sets. To configure binary inputs see paragraph 6.7.2.

Binary input configur.

Binary input configuration

Status

BIN 1

Status

BIN 2

Selected

Parameter set

0 X A

Binary input 1 to
Binary input 2 not to parameter set selection

1 X B

X 0 C

Binary input 1 not to parameter set selection
Binary input 2 to

X 1 D

0 0 A

0 1 B

1 0 C

Binary input 1 to and
Binary input 2 to

1 1 D


For delay in switching between Parameter sets B and A see Paragraph 6.7.13 Change-over delay.

7.3.3 Limits

User defined upper and lower limits allow wide or narrow hysteresis to be set. Unless otherwise required we
recommend a hysteresis of 10%.