Operating Instructions SWT-2000
DYNALCO
13
6.4 Configuration Software
Configuration User and Process User
SWT-2000 parameters are divided into 2 groups, Configuration and Process parameters.
When the program is started, the window shows 3 log in levels, Config user, Process user or Guest. Process
and Configuration users require passwords.
As a Guest one only has the right to view measured data or print out actual parameters.
A Process user can perform Guest functions and view and change Process parameters.
The Configuration user has full access and control over all Parameters, Process as well as Configuration.
The factory settings are shown below Bold.
6.4.2 Log in
Here you can Log in on three different levels. The standart passwords for Config- and Process- User are:
Config user password
1981
Process user password
1977
6.4.3 Main Window and System Limit Matrix
After successfully logging in you will see the main window used for displaying system and measurement
status.
On the left the various System Limit inputs are listed. In the middle the System Limit and alarm status are
shown and on the right all outputs and current levels can be seen.
In the middle is a bar called System limit Matrix. Click on this and an overview of the logical status of System
Limits, binary inputs and sensor error is shown.
6.4.4 Logging In and Out
To change user level log out via
password.
6.5 Configuration File
6.5.1 …creating new
To create a new configuration file go to
Note
: If you have not saved the live parameters, they will be lost.