SW-50 Speed Switch

Installation and Calibration Instructions

Installation: Mount the SW-50 to a secure bracket off the engine. If on-engine

mounting is necessary, shock mounts are recommended. Wire according
to connection diagram on reverse. Shielded cable is recommended. Shield
should be brought to ground directly. The SW-50 will work with most
magnetic pickups provided the signal amplitude is greater than 50 mVrms
and less than 70 Vrms. Mount pickup according to manufacturer’s
instructions.

Calibration: Determine the setpoint frequencies from an RPM value using

the following formula:

Frequency =

RPM x No. of Teeth (Holes)

60

Verify current calibration: Connect a signal generator — such as the Dynalco

F-16 — to the SW-50 magnetic pickup input (signal input).

J

Set the signal generator to a low frequency. Slowly increase the frequency.
Using an ohmmeter across each relay contact, in turn, determine the
frequency at which the relays change state. (Note: overspeed relay will
latch if terminal 4 is not grounded.)

Change the setpoints: Remove the screws in the access holes for the relay

adjustment trim pots.

J

Set the signal generator to the frequency at which the relay should change
state.

J

Using a small, flat screwdriver, adjust the trim pot for the appropriate relay
until the relay changes state.

J

Decrease the frequency, then slowly increase it to verify that the relay trips
at the appropriate point.

SW-50 is a trademark of Dynalco Controls

DYNALCO CONTROLS RESERVES THE RIGHT TO CHANGE THESE SPECIFICATIONS WITHOUT NOTICE.