Installation and Calibration Instructions
Installation: Mount the SW-50 to a secure bracket off the engine. If on-engine
mounting is necessary, shock mounts are recommended. Wire according
to connection diagram on reverse. Shielded cable is recommended. Shield
should be brought to ground directly. The SW-50 will work with most
magnetic pickups provided the signal amplitude is greater than 50 mVrms
and less than 70 Vrms. Mount pickup according to manufacturer’s
instructions.
Calibration: Determine the setpoint frequencies from an RPM value using
the following formula:
Frequency =
RPM x No. of Teeth (Holes)
60
Verify current calibration: Connect a signal generator — such as the Dynalco
F-16 — to the SW-50 magnetic pickup input (signal input).
J
Set the signal generator to a low frequency. Slowly increase the frequency.
Using an ohmmeter across each relay contact, in turn, determine the
frequency at which the relays change state. (Note: overspeed relay will
latch if terminal 4 is not grounded.)
Change the setpoints: Remove the screws in the access holes for the relay
adjustment trim pots.
J
Set the signal generator to the frequency at which the relay should change
state.
J
Using a small, flat screwdriver, adjust the trim pot for the appropriate relay
until the relay changes state.
J
Decrease the frequency, then slowly increase it to verify that the relay trips
at the appropriate point.