667 Adjust Menu (2 of 2)

The Cold Weather Cut Off temperature for the
snow melting system.

The maximum supply water temperature for the
mixing system.

-30 to 50°F
(-34 to 10°C)

Default = 10°F (-12°C)

80 to 210°F, OFF
(27 to 99°C, OFF)

Default = 150°F (66°C)

B1

Item Field

Access
Level

Description

Range

Actual

Setting

Section

LT

D

USER

INS

T

AD

V

A

C

B1

C1

A

C1

C1

C1

A

SUP, RET, NONE

Default = SUP

The location of the boiler sensor. This affects
operation of the boiler contact.

OFF, 80 to 180°F
(OFF, 27 to 82°C)

Default = 140° (60°C)

10 to 70°F, OFF
(5 to 39°C, OFF)

Default = OFF

The maximum

∆T for the snow melting system.

The differential for the snow melting system.
Boil SENS = SUP

The minimum temperature allowed for the boiler
target temperature.

Boil SENS

NONE

AUTO, 2 to 42°F
(AUTO, 1 to 23°C)

Default = AUTO

The time delay the control can expect between
the time the boiler contact closes and the
boiler fires.

Boil SENS = SUP

0:00 to 3:00 minutes

Default = 0:10 min

LITE, MED, HEVY

Default = MED

The thermal mass characteristics of the boiler
that is being used.

Boil SENS = SUP

The frequency with which the control exercises
the pumps and valves that are operated by
the control.

30 to 240 hours,
(in 10 hour steps)

Default = 70 hr