beautypg.com

Technical data, Limited warranty and product return procedure, Surface, melting – tekmar 662 Snow Detector & Melting Control User Manual

Page 12: Surface, idling, Water sensitivity, Maximum supply, Min. boiler return, T max, Cwco, Motor speed

background image

12

The installer must ensure that this control and its wiring are shielded from strong sources of electromagnetic noise. Conversely, this electronic
control does not exceed Class B limits for radio noise emissions from digital apparatus as set out in the Radio Interference Regulations of
the Canadian Department of Communications. If this equipment does cause interference, the user is encouraged to try to correct the
interference by reorientating the receiving antenna and/or relocating the receiver with respect to this equipment. Le présent numérique
n'émete pas de bruits radioeléctriques dépassant les limites applicables aux appareils numériques de Classe B prescrites dans le réglement
sur le brouillace radioeléctrique édicté par le Ministére des Communications du Canada.

Limited Warranty The liability of tekmar Control Systems Ltd. and tekmar
Control Systems, Inc. (“tekmar”) under this warranty is limited. The purchaser,
by taking receipt of the tekmar product (“product”), acknowledges receipt of
the terms of the warranty and acknowledges that it has read and
understands same.

tekmar warrants each tekmar product against defects in workmanship and materi-
als, if the product is installed and used in compliance with tekmar's instructions. The
warranty period is for a period of twenty-four (24) months from the production date
if the product is not installed during that period, or twelve (12) months from the
documented date of installation if installed within twenty-four (24) months from the
production date.

The liability of tekmar under this warranty shall be limited to, at tekmar's sole dis-
cretion: the cost of parts and labor provided by tekmar to repair defects in materials
and/or workmanship of the defective product; or to the exchange of the defective
product for a replacement product; or to the granting of credit limited to the original
cost of the defective product, and such repair, exchange or credit shall be the sole
remedy available from tekmar, and, without limiting the foregoing in any way,
tekmar is not responsible, in contract, tort or strict product liability, for any
other losses, costs, expenses, inconveniences, or damages, whether direct, indi-
rect, special, secondary, incidental or consequential, arising from ownership or use
of the product, or from defects in workmanship or materials, including any liability
for fundamental breach of contract.

This warranty applies only to those products returned to tekmar during the
warranty period. This warranty does not cover the cost of the parts or labor
to remove or transport the defective product, or to reinstall the repaired or

Limited Warranty and Product Return Procedure

replacement product. Returned products that are not defective are not cov-
ered by this warranty.

This warranty does not apply if the product has been damaged by negligence
by persons other than tekmar, accident, fire, Act of God, abuse or misuse; or
has been damaged by modifications, alterations or attachments made sub-
sequent to purchase which have not been authorized by tekmar; or if the
product was not installed in compliance with tekmar’s instructions and the
local codes and ordinances; or if due to defective installation of the product;
or if the product was not used in compliance with tekmar’s instructions.

This warranty is in lieu of all other warranties, express or implied, which the
Governing Law (being the law of British Columbia) allows parties to contrac-
tually exclude, including, without limitation, warranties of merchantability,
fitness for a particular purpose, durability or description of the product, its
non-infringement of any relevant patents or trademarks, and its compliance
with or non-violation of any applicable environmental, health or safety legis-
lation; the term of any other warranty not hereby contractually excluded is
limited such that it shall not extend beyond twenty-four (24) months from the
production date, to the extent that such limitation is allowed by the Govern-
ing Law.

Product Return Procedure Products that are believed to have defects in work-
manship or materials must be returned, together with a written description of the
defect, to the tekmar representative for that territory. If the address of the repre-
sentative is not known, please request it from tekmar at the telephone number
listed below

.

All specifications are subject to change without notice.

Printed in Canada on recycled paper.

Product design, software and literature are Copyright © 1999 by:
tekmar Control Systems Ltd. and tekmar Control Systems, Inc.

tekmar Control Systems Ltd., Canada
tekmar Control Systems, Inc., U.S.A.
Head Office: 4611 - 23rd Street
Vernon, B.C. Canada V1T 4K7
Tel. (250) 545-7749 Fax. (250) 545-0650
Web Site: www.tekmarcontrols.com

Control Systems

Snow Detector & Melting Control 662

Floating / Variable Speed / 4-20 mA

Literature

— D 662, A 662’s, D 001, D 070, E 021.

Control

— Microprocessor PID control; This is not a safety (limit) control.

Packaged weight

— 4.1 lb. (1900 g), Enclosure A, blue modified PPO plastic

Dimensions

— 6-5/8” H x 7-9/16” W x 2-13/16” D (170 x 193 x 72 mm)

Approvals

— CSA NRTL/C, meets ICES & FCC regulations for EMI/RFI.

Ambient conditions

— Indoor use only, 30 to 105

°F (0 to 40°C), < 90% RH non-

condensing.

Power

— 120 V (ac)

±10% 50/60 Hz 300 VA

System Pumps

— 120 V (ac) 6 A 1/3 hp, pilot duty 240 VA 2 A

Variable Pump

— 120 V (ac) 50/60 Hz 2.2 A 1/6 hp, internally fused

Mix Relays

— 24 V (ac) 10 A, pilot duty 48 VA 2 A

Other Relays

— 120 V (ac) 10 A 1/3 hp, pilot duty 240 VA 2 A

Sensors included

— NTC thermistor, 10 k

Ω @ 77°F (25°C ±0.2°C) ß=3892

Outdoor Sensor 070, Slab Sensor 072, & 3 of Universal Sensor 071

Optional devices

— tekmar Type #: 011, 031, 090, 091.

Detection of Snow/Ice — Down to -20

°F (-29°C) in calm air with 500 feet (150 m) of 18

AWG wire to Snow/Ice Sensor 090.

Surface, Melting

— 34 to 44

°F (1 to 7°C)

Surface, Idling

— Off, 24 to 35

°F (Off, -5 to 2°C)

Water Sensitivity

— 20 to 80%

Maximum Supply

— 100 to 200

°F (38 to 93°C)

Min. Boiler Return

— Off, 55 to 150

°F (Off, 13 to 66°C)

∆T Max

— 10 to 50

°F (6 to 28°C)

CWCO

— Off, -22 to 25

°F (Off, -30 to -4°C)

Motor Speed

— 30 to 230 seconds

Temperature display

— Fahrenheit / Celsius

Snow Detector & Melting Control 662

Floating / Variable Speed / 4-20 mA

Test

Do not apply power here

Power

Remote

Item

Max. Supply

30

130 sec

230

Motor Speed /

Pump Response

CWCO

10

30

°F

50

∆T Max.

Sensitivity

Melting

Min. Boil Return

Idling

29

°F

Off

35

24

50 %

20

80

Surface

39

°F

34

44

100

°F

Off

150

60

150

°F

100

200

0

°F

-20

25

Red
Sen

Blk

Sen

Blu

Sen

17

18 19 20 21 22 23 24 25 26 27 28

Yel

Sen

Brn

Sen

Com

Sen

Rem

En

Bret
Sen

Com

Sen

Ret

Sen

Sup
Sen

Out
Sen

1

2

Melt

3

4

Boiler

11 12 13 14 15 16

4-20

+

Pump 1

Pump 2

Opening

Boiler

Warning

Closing

CWCO

Melting

Idling

WWCO

Maximum

∆T

Maximum
Supply

Minimum
Return

Water

Supply

Usage (

∆T x hrs)

Slab

Boiler Return

Actual

∆T

% Output

To change between

°F and °C, press and

hold for 1 sec.

120 V (ac)

±10% 50/60 Hz 300 VA

120 V (ac) 6 A 1/3 hp, pilot duty 240 VA 2 A
120 V (ac) 50/60 Hz 2.2 A 1/6 hp, internally fused
24 V (ac) 10 A, pilot duty 48 VA 2 A
120 V (ac) 10 A 1/3 hp, pilot duty 240 VA 2 A

Power
System Pumps
Variable Pump
Mix Relays
Other Relays

Made in Canada by
tekmar Control Systems Ltd.

tekmar

010

Opn

Mix

Cls
Mix

Warning

5

6

9

7

8

P1

Pmp

P2

Pmp

Com
Pmp

Power

L

N

Var

Pmp

Use Nº 20 AWG or larger copper conductors rated for at least 75

°C / 300V

Target

∆T

The Snow/Ice Sensor is installed in a
hostile environment. It should be cleaned
and checked on a regular basis.

10

Off

F C

OUTSIDE

29

Com

Mix

1000

4-20

R

NRTL /C

LR 58223

Jan 98

1234567

tekmar

011