Adjus t menu – tekmar 279 Steam Control User Manual
Page 19

19 of 24
© 2010 D 279 - 05/10
ADJUS
T MENU
Item Field
Range
Access
Description
Actual Setting
35 to 100°F
(1.5 to 38.0°C)
Default = 65°F
(18.5°C)
User
WARM WEATHER SHUT DOWN
OCCUPIED
SECTION I
Select the steam system’s warm weather shut
down temperature during the occupied period.
WWSD does not affect DHW Tankless Coil
operation.
35 to 100°F
(1.5 to 38.0°C)
Default = 60°F
(15.5°C)
User
WARM WEATHER SHUT DOWN
UNOCCUPIED
SECTION I
Select the steam system’s warm weather shut
down temperature during the unoccupied period.
WWSD does not affect DHW Tankless Coil
operation.
Available when:
Setback/Off switch setting is set to Setback.
•
°F or °C
Default = °F
User
TEMPERATURE UNITS
Select to display temperature in °F or °C.
Adjust Menu (3 of 3)
Note: The Setback / Off switch setting must be in the Setback position in order to have access to the TIME menu.
Setting the Time
Time Menu
Step 1
Press and release the Menu button until the TIME menu is reached.
Step 2
Press the Item button. While the minutes are flashing, use the or button to set the minutes.
Step 3
Press and release the Item button. While the hours are flashing, use the or button to set
the hour.
Step 4
Press and release the Item button. While the day is flashing, use the or button to set the day.
Step 5 (Only available in Installer access level)
Press and release the Item button. Use the or button to select between 12 and 24 hour time.
After the last item, the control returns to the first item in the menu.