beautypg.com

tekmar 268 Boiler Control User Manual

Page 12

background image

© 2010

D 268 - 11/10

12 of 32

Section E1

DHW

Section E: Domestic Hot Water Operation

Section E1: Domestic Hot Water (DHW)

DHW DEMAND

A DHW Demand is required in order for the control to provide heat to the DHW system. A DHW aquastat or setpoint control is used
as a switch in the DHW demand circuit. Once the control detects a DHW demand, the DHW Demand pointer turns on in the LCD
and the control operates the boiler to provide a sufficient boiler supply water temperature to the DHW tank. The control operates
the pumps as described below.
The control registers a DHW Demand when a voltage between 24 and 230 V (ac) is applied across the Setp / DHW and Com Dem
terminals (8 and 7).

BOILER TARGET DURING DHW GENERATION

The boiler target temperature is at least as hot as the DHW exchange setting (DHW XCHG). The DHW demand overrides the boiler
reset target temperature, except when the boiler reset target is higher than that of the DHW exchange setting.

DHW MODE & PRIORITY OPERATION

The control has five different settings available for DHW MODE. The required DHW MODE setting will depend on the piping
arrangement of the DHW tank.

It is often desirable to have a priority for the DHW allowing for quick recovery of the DHW tank temperature. This is achieved by
limiting or even stopping the flow of heat to the heating system when the DHW tank calls for heat.

DHW MODE OFF – No DHW

The DHW feature is not selected. This allows for Setpoint operation as described in section F.

DHW

Pump

Primary

Pump

Boiler
Pump

DHW

Pump

Primary

Pump

Boiler
Pump

DHW

Pump

Primary

Pump

Boiler
Pump

DHW MODE 2 – DHW in Parallel with Priority

When a DHW Demand is present, the Relay 9 / DHW contact (terminals
30 and 31) closes and the primary pump contact is opened.
It is assumed that the DHW pump will provide adequate flow
through the heat exchanger and the boiler.

DHW MODE 3 - DHW in Primary / Secondary no Priority

When a DHW Demand is present, the Relay 9 / DHW contact (terminals
30 and 31) is closed and the primary pump contact is closed.
This mode can be used if a DHW tank is piped in direct return and
a DHW valve is installed.

DHW MODE 1 – DHW in Parallel no Priority

When a DHW Demand is present, the Relay 9 / DHW contact (terminals
30 and 31) closes with the DHW demand. The primary pump does not
turn on, but may operate based on a Boiler Demand or External Input
Signal. Refer to sections E and G.
It is assumed that the DHW pump will provide adequate flow
through the heat exchanger and the boiler.