beautypg.com

tekmar 264 Boiler Control User Manual

Page 4

background image

©

2008 D

264

-

12/08

4

of

32

Section A

General

Operation

Page 4 - 6

Section B

Staging

Operation

Page 6 - 8

Section C

Pump

Operation

Page 8 - 9

Section D

Boiler Reset

Operation

Page 9 - 11

POWERING UP THE CONTROL

When the control is powered up, all segments in the LCD are turned on for 2 seconds. Next, the control displays the control type
number in the LCD for 2 seconds. Next, the software version is displayed for 2 seconds. Finally, the control enters into the normal
operating mode.

OPERATION

The control operates up to four on / off heat sources to control the supply water temperature to a hydronic system. The supply water
temperature is based on either the current outdoor temperature or a fixed setpoint.

Section E

DHW

Operation

Page 12 - 14

Decreasing Outdoor Temperature

Incr

easing W

a

ter T

e

mperatur

e

Terminal Unit

Terminal Unit

Indoor Design

Indoor Design

Outdoor Design

Outdoor Design

Design Supply

Design Supply

1

Com

2

Boil

Sup

3

Boil

Ret

4

Out

5

UnO

Sw

Timer Switch

The following defined terms and symbols are used throughout this manual to bring attention to the presence of hazards of various risk
levels, or to important information concerning the life of the product.

INSTALLATION

CATEGORY II

- Warning Symbol: Indicates presence of hazards which can cause severe personal injury, death or

substantial property damage if ignored.

- Double

insulated

- Local level, appliances

Definitions

Sequence Of Operation

Section A: General Operation

Section F

Setpoint

Operation

Page 15 - 15

Boiler Reset

When a boiler demand signal from the heating system is present, the control operates
the boiler(s) to maintain a supply temperature based on the outdoor air temperature and
Characterized Heating Curve settings.

Domestic Hot Water

When a DHW demand signal from a DHW aquastat is present, the control operates the
boiler(s) to maintain the supply water temperature at least as hot as the DHW XCHG setting.
Refer to section E.

SETBACK

(UNOCCUPIED)

To provide greater energy savings, the control has a setback feature. With setback, the
supply water temperature in the system is reduced when the building is unoccupied. By
reducing the supply water temperature, the air temperature in the space may be reduced
even when a thermostat is not turned down. Any time the UnO Sw (5) and the Com (1) are
shorted together, the control operates in the UnOccupied mode. When in the UnOccupied
mode, the UNOCC segment is displayed in the LCD. The control adjusts the supply water
temperature based on the UNOCC settings made in the control.

Setpoint

When a setpoint demand signal from a setpoint system is present, the control operates the boiler(s) to maintain the supply water
temperature at least as hot as the SETP setting. Refer to section F.

External Input 0 - 10 V (dc) or 2 - 10 V (dc)

When an external input signal is present, the control converts the signal to a target supply temperature. The control operates the
boiler(s) to maintain the required supply water temperature.

Section G

External Input

Operation

Page 16 - 17