tekmar 264 Boiler Control User Manual
Page 29

29 of 32
© 2008 D 264 - 12/08
Adjust Menu (4 of 4)
Display
Description
Range
Section
Installer
Ad
vanced
Actual
Setting
D1
WWSD UnOccupied The system’s warm weather shut
down temperature during the UnOccupied period.
35 to 100°F, OFF
(2 to 38°C, OFF)
Default = 60°F (16°C)
C1
Primary Pump Purge
The maximum length of time that the primary pump will
continue to operate after the boiler demand has been
removed.
OFF, 0:10 to 19:55 min
Default = 0:20 min
C1
Boiler Pump Purge
The length of time that the boiler pump will continue to
run after the last stage in the boiler has turned off. (This
item is only available in modes 2 and 4.)
OFF, 0:10 to 19:55 min
Default = 0:20 min
A
Boiler Alarm The alarm signal will be activated if the
boiler supply temperature does not increase within the
selected time. (This item is only available when the Alarm
/ C.A. DIP switch is set to Alarm.)
OFF, 3 to 40 min
(1 minute increments)
Default = 20 min
Units The units of measure that all of the temperatures
are to be displayed in by the control.
°F, °C
Default = °F
- 032 Timer (4 pages)
- 033 4 Timer (12 pages)
- 040 RDM (4 pages)
- 054 RTU (2 pages)
- 055 RTU (2 pages)
- 060 RTU (2 pages)
- 062 RTU (4 pages)
- 063 RTU (8 pages)
- 070 Outdoor Sensor (4 pages)
- 071 Universal Sensor (4 pages)
- 072 10k Slab Sensor (2 pages)
- 073 10k Slab Sensor (2 pages)
- 076 Indoor Sensor (4 pages)
- 077 Indoor Sensor (4 pages)
- 078 Universal Sensor (4 pages)
- 079 Slab Sensor (4 pages)
- 081 Three Outdoor Sensor Module (4 pages)
- 082 Universal Sensor (4 pages)
- 083 Duct Sensor (4 pages)
- 084 Indoor Sensor (4 pages)
- 085 10k Solar Sensor (2 pages)
- 086 Humidity & Temperature Sensor (8 pages)
- 090 Snow/Ice Sensor (8 pages)
- 095 Snow Sensor (8 pages)
- 150 One Stage Setpoint Control (4 pages)
- 152 Two Stage Setpoint Control (4 pages)
- 153 Mixing Setpoint Control (4 pages)
- 155 Difference Setpoint Control (4 pages)
- 156 Difference Setpoint Control (12 pages)
- 157 Difference Setpoint Control (16 pages)
- 161 Setpoint Control Installation (36 pages)
- 161 Setpoint Control User Manuals (12 pages)
- 162 Setpoint Control Installation (32 pages)
- 162 Setpoint Control User Manuals (12 pages)
- 256 Boiler Control (20 pages)
- 257 DHW Control (12 pages)
- 260 Boiler Control (20 pages)
- 261 Boiler Control (20 pages)
- 262 Boiler Control Installation (36 pages)
- 262 Boiler Control User Manuals (4 pages)
- 263 Boiler Control (36 pages)
- 265 Boiler Control (36 pages)
- 268 Boiler Control (32 pages)
- 269 One Stage Steam Control (12 pages)