Adjust Menu (4 of 4)

Display

Description

Range

Section

Installer

Ad

vanced

Actual

Setting

D1

WWSD UnOccupied The system’s warm weather shut
down temperature during the UnOccupied period.

35 to 100°F, OFF
(2 to 38°C, OFF)
Default = 60°F (16°C)

C1

Primary Pump Purge
The maximum length of time that the primary pump will
continue to operate after the boiler demand has been
removed.

OFF, 0:10 to 19:55 min
Default = 0:20 min

C1

Boiler Pump Purge
The length of time that the boiler pump will continue to
run after the last stage in the boiler has turned off. (This
item is only available in modes 2 and 4.)

OFF, 0:10 to 19:55 min
Default = 0:20 min

A

Boiler Alarm The alarm signal will be activated if the
boiler supply temperature does not increase within the
selected time. (This item is only available when the Alarm
/ C.A. DIP switch is set to Alarm.)

OFF, 3 to 40 min
(1 minute increments)
Default = 20 min

Units The units of measure that all of the temperatures
are to be displayed in by the control.

°F, °C
Default = °F