beautypg.com

E-stop safety module, Model es-fa-6g, E-stop safety module product specifications – Banner ES-FA-6G Safety Module User Manual

Page 10

background image

E-Stop Safety Module

– Model ES-FA-6G

page

10

Supply Protection Circuitry

Dimensions

See Figure 4.

Protected against transient voltages and reverse polarity

Output Configuration

Outputs (K1 & K2):

three redundant (total of six) safety relay (forced-guided) contacts – AgSnO

2

one auxiliary non-safety monitor output (open when both K1 and K2 are energized;
closed when either K1 or K2 are de-energized)

Contact ratings:

Maximum voltage: 250V ac or 250V dc
Maximum current: 6 A ac or dc
Minimum current: 30 mA @ 10V dc
Maximum power: 1500VA, 150W
Mechanical life: 10,000,000 operations
Electrical life: 100,000 at full resistive load

NOTE: Transient suppression is recommended when switching inductive loads. Install suppressors
across load. Never install suppressors across output contacts (see Warning, page 5).

Output Response Time

35 milliseconds typical

Status Indicators

3 green LED indicators:
Power ON
K1 energized
K2 energized

Input Requirements

E-stop switch must have a normally closed contact capable of switching 40 to 100mA @ 13 to 27V ac/dc.
Reset switch must have one normally open contact capable of switching 20 to 30mA @ 13 to 27V ac/dc.

Housing

Polycarbonate. Rated NEMA 1; IEC IP40, Terminals IP20

Mounting

Mounts to standard 35 mm DIN rail track. Safety Module must be installed inside an enclosure rated NEMA 3
(IEC IP54), or better.

Vibration Resistance

10 to 55Hz @ 0.35mm displacement per IEC 68-2-6

Operating Conditions

Temperature:

0° to +50°C (+32° to 122°F)

Maximum Relative Humidity: 90% @ +50°C (non-condensing)

Supply Voltage and Current

24V ac/dc, +/- 10%; 50/60Hz
Power consumption: approx. 2W/0.75VA

E-Stop Safety Module Product Specifications