beautypg.com

1 communications setup, 1 ping routine, Control module configuration – Banner A-GAGE High-Resolution MINI-ARRAY Series User Manual

Page 17

background image

17

Banner Engineering Corp.

Minneapolis, U.S.A.

www.bannerengineering.com • Tel: 763.544.3164

P/N 64118 rev. B

Control Module Configuration

Banner Engineering Corp.

Minneapolis, U.S.A.

www.bannerengineering.com • Tel: 763.544.3164

Figure 5-1. Options menu, serial port

selection

Figure 5-2. MINI-ARRAY menu

Figure 5-3. Screen showing the result of a

completed Ping routine

5. Control Module Configuration

The A-GAGE High-Resolution MINI-ARRAY control module is easily configured using a

Windows® menu-style routine; the configuration routine requires the Banner-supplied

HRMA software and a PC-compatible computer (running Windows® XP, Vista, or 7)

A serial data connection is made between the computer and the DB9 connector on the

control module.

5.1 Communications Setup

After installing the software, attach the serial communication cable between the control

module and the PC. (NOTE: If an RS-232 interface is used, only one control module is

allowed on the line at any one time.) The minimum connections to the control module’s

DB-9 connector are shown in Figure 3-8.

Launch the High-Resolution MINI-ARRAY program and configure the serial

communications port of the PC. Select the Options menu from the High-Resolution

MINI-ARRAY main menu (see Figure 5-1). The program supports serial communication

via the

COM1-COM20.port of the computer. Highlight the desired

serial port to select it (a “bullet” will appear next to the selected option), then select

Save Settings on Exit to store the serial port selection, if it is not already ON (a

“bullet” will appear next to the option, if it is ON).

Parity is selected here also: Even, Odd or None.

5.1.1 Ping Routine

The Ping routine must be performed during System configuration, and before any

Diagnostic, Alignment, or Edit routine. The routine polls all control modules on the

communications line (one, in the case of the standard RS-232 line, or up to 15

modules, on an RS-485 circuit). It then is used to select an individual control module

for configuration or alignment.

If needed, apply power to the System control module and allow the System to

complete its power-up routine. Press F5 or access the MINI-ARRAY menu and select

Ping to perform the Ping routine. All connected control modules will then identify

themselves with an ID value and baud rate; the routine takes approximately 15 to 20

seconds. After the Ping is performed, all valid control module ID values will appear in a

chart on the screen, under their appropriate baud rates (see Figure 5-3). Control

modules are identified in the chart as ‘X.’ Point to a valid ID with the mouse pointer

and click to select a control module. System Diagnostics, Alignment, or Edit routines

may now be performed for the selected control module.