Rockwell Automation GV3000 AC Pwr Module Ver. 5.0 Hardware Ref, Installation, and Troubleshooting User Manual
Page 66

7Ć10
Table 7.1 Ć Wiring Signal and Control I/O to the Terminal Strip (Continued)
БББББ
Б
БББ
Б
БББББ
Terminal
Number
ББББББББББ
Б
ББББББББ
Б
ББББББББББ
Description
ББББББББББББББББББ
Б
БББББББББББББББББ
ББББББББББББББББББ
Parameters/Wiring Connections
БББББББББББББББББББББББББББББББ
БББББББББББББББББББББББББББББББ
Wiring a Remote/Local Input
16
+24 VDC Power Supply
Current limited for remote input logic use only.
БББББ
БББББ
17
ББББББББББ
ББББББББББ
Digital Input 8
(Default Ć Remote/Local)
ББББББББББББББББББ
ББББББББББББББББББ
Digital input 8 is control function programmable through
parameter P.007.
БББББББББББББББББББББББББББББББ
Б
ББББББББББББББББББББББББББББББ
Б
Б
ББББББББББББББББББББББББББББББ
Б
Б
ББББББББББББББББББББББББББББББ
Б
Б
ББББББББББББББББББББББББББББББ
Б
Б
ББББББББББББББББББББББББББББББ
Б
Б
ББББББББББББББББББББББББББББББ
Б
Б
ББББББББББББББББББББББББББББББ
Б
ББББББББББББББББББББББББББББББББ
WARNING
IF A MAINTAINED START CONTACT IS USED WHEN THE CONTROL SOURCE = rE,
SWITCHING FROM LOCAL TO REMOTE FROM THE TERMINAL STRIP WILL CAUSE POWER
TO BE APPLIED TO THE MOTOR IF THE REMOTE START CONTACT IS CLOSED. STAY CLEAR
OF ROTATING MACHINERY IN THIS CASE. FAILURE TO OBSERVE THIS PRECAUTION COULD
RESULT IN BODILY INJURY.
The following parameters must be set:
P.000: Control Source
(Only active when P.000 = rE)
P.006: Second Menu Password
P.007: Terminal Strip Digital Inputs Configure (Selects
and assigns a control function to digital inputs
6 to 8).
P.008: Terminal Strip Speed Reference Source
(Analog, Motor Operated Potentiometer (MOP), or
Preset Speeds)
Note that based on the settings of parameters P.000, P.007,
P.008, and r.030 if an RMI board is used, the following
parameters can affect digital input 8.
P.023: MOP Accel/Decel Time
P.024: MOP Reset Configuration
P.031 to P.038: Preset Speeds 1Ć8
Refer to the GV3000 Programming instruction manual
(D2Ć3339) for additional information.
Terminal 17 On = Local Control
Diagram shows factory setting.