Rockwell Automation FactoryTalk Historian SE 3.0 UniInt Interface User Guide User Manual
Page 75
![background image](/manuals/581131/75/background.png)
UniInt Interface User Manual
69
29-Nov-06 15:45:08
Historian-WriteSeconds 1> Disconnected Startup is not available with PI API prior
to Version: 1.6, Build 1.5
To utilize the disconnected startup configuration, upgrade to
PI API Version: 1.6, Build 1.5 or later and restart the interface.
Stopping Interface.
Meaning:
The UniInt Cache Manager has found a PI API version currently
installed on the interface node that does not support disconnected
startup. The interface has been configured with the /CacheMode
startup parameter and will be stopped.
Resolution:
Option 1: Upgrade the PI API on the interface node to version 1.6.1.x
or later. Restart the interface.
Option 2: Remove the /CacheMode startup command parameter.
Restart the interface.
29-Nov-06 15:56:19
Historian-WriteSeconds 1> Error: 0, Setting cache function pointer failed.
Unable to load picm_closecache from API dll
Point caching unavailable for this interface.
Correct the error or remove the /cachemode startup command parameter.
Stopping Interface.
Meaning:
The UniInt Cache Manager has failed to load a required function from
the PI API. The interface has been configured with the /CacheMode
startup parameter and will be stopped.
Resolution:
Option 1: Upgrade the PI API on the interface node to version 1.6.1.x
or later. Restart the interface.
Option 2: Remove the /CacheMode startup command parameter.
Restart the interface.
29-Nov-06 15:56:19
Historian-WriteSeconds 1> Error 0: The /uiinfops must be defined with a single
character
pointsource value on the startup command-line when using /cachemode
against a Historian Server version ealier than 2.
Intializing uniint library failed
Stopping Interface
Meaning:
The /uiinfops startup command-line parameter is either missing or
has a multi-character point source designated for the interface
information tag. This error occurs when running in a disconnected
startup configuration and connecting to a host Historian Server
version earlier than 2. The interface will be shutdown.
Resolution:
Option 1: Define the /uiinfops startup command-line parameter
with a single character point source. Restart the interface.
Option 2: Remove the /CacheMode startup command parameter to
run in a non-disconnected startup configuration. Restart the
interface.