Controller template overview – Rockwell Automation System Release 3.0 PlantPAx System Application Templates Quick Start User Manual
Page 12
12
Rockwell Automation Publication PROCES-QS001A-EN-P - October 2013
Chapter 1 Configure the Controller Application
Controller Template Overview
Controller templates provide the necessary task configurations that are required for the PlantPAx system. Controller
template options also are provided with pre-loaded PlantPAx Library content if the PlantPAx Library is to be used. Library
content definitions use controller memory, so use the guidance in
when selecting the appropriate template for your
application.
For each controller, you must choose one of three templates to begin system configuration.
show the
templates that are recommended (denoted by ‘X’) based on the selected controller.
IMPORTANT
Controller templates are distributed with the PlantPAx Library of Process Objects. To download the templates, see Knowledgebase
Answer ID 62682 at
Table 2 - PlantPAx Controller Templates and ControlLogix Controllers
Simplex Controllers
Redundant Controllers
1756-L71
1756-L72
1756-L73
1756-L74
1756-L75
1756-L73
1756-L74
1756-L75
User memory
2 MB
4 MB
8 MB
16 MB
32 MB
8 MB
16 MB
32 MB
No library
X
X
X
X
X
X
X
X
Basic library
(1)
(1) Basic library template is approximately 0.4 MB.
X
X
X
X
X
X
X
X
All library
(2)
(2) All library template is approximately 1.2 MB.
X
X
X
X
X
X
Table 3 - PlantPAx Controller Templates and CompactLogix Controllers
1769-L24ER-QBFC1B
1769-L33ER
User memory
0.75 MB
2 MB
No library
X
X
Basic library
(1)
(1) Basic library template is approximately 0.4 MB.
X
X
All library
(2)
(2) All library template is approximately 1.2 MB.
Table 4 - Controller Template Descriptions
Template
Name
(1)
(1) PlantPAx Library 3.0 supports RSLogix 5000 software version 18 and later. Templates are provided with software version 18 so they can be used in any later supported version of RSLogix 5000.
Description
No library
RSL5k_18_Template_PlantPAx_noLib.acd
No PlantPAx Library of Process Objects.
Basic library
RSL5k_v18_Template_PlantPAxLib_3_0_00_basic.acd
(2)
(2) The service release number (boldfaced) can change as service revisions are created.
PlantPAx Library of Process Objects, includes diagnostics and the following Process Add-On
Instructions: P_AIn, P_Alarm, P_AOut, P_DIn, P_Gate, P_DOut, P_Intlk, P_Mode, P_Motor,
P_Perm, P_Reset, P_ValveSO, P_VSD, P_PIDE, T_ADD, T_Clock, T_DST, T_Valid.
All library
RSL5k_18_Template_PlantPAxLib_3_0_00_all.acd
Complete PlantPAx Library of Process Objects.