Adding a mcc unit to an ethernet/ip system – Rockwell Automation 2500 CENTERLINE Motor Control Centers Installation Manual User Manual
Page 80
80
Rockwell Automation Publication 2500-IN001C-EN-P - April 2014
Chapter 9
IntelliCENTER Options
MCC Cable Types
The CENTERLINE 2500 MCCs use a high voltage 600V Ethernet cable
designed to perform above TIA 568-B.2 and ODVA Ethernet standards. These
cables have the following features:
•
Foil and braided shield, PVC, eight conductor (four pair)
•
600V PVC cable designed to support high voltage applications
•
On-machine rated cable for use in a cable tray shared with high voltage
power cables
•
RJ45 insulation displacement connector available for field terminations
•
Wide thermal operating range
Figure 27 - EtherNet/IP Cable Pin-out
Adding a MCC Unit to an EtherNet/IP System
Use this section to add Bulletin 2500 units to an EtherNet/IP MCC. Each
EtherNet/IP component is factory wired within the unit and has a
communication cable that plugs into the device on one end and generally into a
vertical wireway EtherNet/IP port on the other end.
ATTENTION: Do not apply high voltage to any installed EtherNet/IP cable
system or its connectors.
Table 5 - EtherNet/IP Cable Specifications for MCCs
Certifications
UL and cUL Listed
Outside diameter
0.32 ± 0.015 in. (8.13 ± 0.38 mm)
Operating temperature
-20…80 °C
Cable rating
UL, cUL TYPE CMG; UL PLTC or UL AWM 2570 80C 600V, TIA 568B
Pin No.
Cable Color
Description
1
White/Orange
TxData +
2
Orange
TxData -
3
White/Green
Recv Data +
4
Blue
Unused
5
White/Blue
Unused
6
Green
Recv Data -
7
White/Brown
Unused
8
Brown
Unused
No. of
Conductors
Jacket Material
Cable Type
Cable Rating
Cat. No.
(1)
(1) Replace -2 (2 m) with -5 (5 m), or -10 (10 m) for additional standard cable lengths.
8
Teal 600V PVC
Foil and braided
shield
(UL) CMX, CMR; c(UL) CMG; (UL) PLTC
or AWM 2570 80 °C 600V; TIA-568-B
1585J-M8HBJM-2
Red 600V PVC
1585J-M8EBJM-2
8
7
6
5
4
3
2
1