Dimensions – Rockwell Automation 2500 CENTERLINE Motor Control Centers Installation Manual User Manual
Page 14

14
Rockwell Automation Publication 2500-IN001C-EN-P - April 2014
Chapter 1
System Overview
Dimensions
CENTERLINE 2500 MCCs are designed in widths between 600 and 1,000 mm.
Each column is 2300 mm high and either 600 mm or 800 mm deep. Double-front
columns are also available. See the column tables below for additional options.
Unit size is described in terms of modules. Each module is approximately 80 mm
high. Columns can accommodate 24 modules of varying unit combinations.
Figure 2 - Typical Column Dimensions
All measurements are in mm unless otherwise specified.
Table 2 - Column Width
Total Column Width
Unit Width
Vertical Wireway Width
600
(1)
(1) Only for full-column, frame mount applications.
600
No vertical wireway
700
500
200
800
300
900
400
1000
500
Table 3 - Column Depth
Single-front
Double-front
600
1200
800
1600 or 2000
(1)
(1) 800 mm columns can be mounted in a double-front
arrangement on site. A 400 mm air gap is required
between 3200 A and 4000 A double-front columns.
Table 4 - Column Height
Dimension
Measurement
Total Height
2300
Available Unit Height
1980
Top Horizontal Wireway
170
Bottom Horizontal Wireway
115
External Mounting Channel
35
170
1980
35
115
600…1000
600 or 800
2300
200…500
(1)
500 or 600
(1)
(1) Vertical wireway dimensions apply only to 500 mm wide units.