5-4
Start and Adjustment
Step 1. Power Up the 8720MC-RPS Regenerative Power
Supply
This step verifies that the 8720MC-RPS Regenerative Power
Supply powers up and passes the power-up self-diagnostics. After
the unit passes the diagnostics, the operation panel automatically
enters monitor mode, with input current displayed.
Step 1.1
Turn power ON.
The initial display shows SELF,
with all six status LEDs ON,
indicating the unit is performing
power-up self-diagnostics.
After the diagnostics are
complete (approx. 0.5 seconds),
the operation panel is in
monitor mode. The display
shows input current value, and
the "A" status LED turns ON.
This display shows that the
input current is 0 Amp.
Step 2.
Verifying the Parameter of the Unit Selection
In this step, you will verify that the unit rating matches the
parameter setting of the Unit Selection.
Step 2.1
Press the PRG key.
The operation panel changes to
program mode and the
"PROGRAM" status LED turns
ON. The display shows "U.---"
indicating you can access the
User parameters.
Step 2.2
Press the
key.
The display shows "F.---"
indicating that the Factory
parameters can be accessed.
Step 2.3
Press the ENT key.
The display shows the first
Factory parameter (F.000).
RST PRG ENT
READY
READY
FAULT
FAULT
PROGRAM
PROGRAM
kW
kW
V
A
RST PRG ENT
READY
READY
FAULT
FAULT
PROGRAM
PROGRAM
kW
kW
V
A
RST PRG ENT
READY
READY
FAULT
FAULT
PROGRAM
PROGRAM
kW
kW
V
A
RST PRG ENT
READY
READY
FAULT
FAULT
PROGRAM
PROGRAM
kW
kW
V
A
RST PRG ENT
READY
READY
FAULT
FAULT
PROGRAM
PROGRAM
kW
kW
V
A