Rockwell Automation 8720MC 8720MC Regenerative Power Supply User Manual User Manual
Page 24
2-12
About 8720MC-RPS Regenerative Power Supply
Terminal Name
Control Power Terminals
Terminals to Connect
Precharge/Discharge
Resistor
Control Terminals for
Main Magnetic Contactor
Symbol
L
1AUX,
L
2AUX,
L
3AUX
PR1,
PR2,
PR3
MC1,
MC2
Description
To connect three-phase AC input power to the
control circuit.
For 460 V unit: 380 to 460 VAC +10%, -15%,
50/60 Hz +/-5%
To connect precharge/discharge resistor.
When the built-in resistor is used:
Jumper between PR2 and PR3, and open
PR1.
When an external resistor is used:
Connect the resistor between PR1 and
PR2, and open PR3.
When the unit is connected for power
regeneration mode only:
Open all the terminals PR1, PR2 and
PR3.
To be used as the control terminals for the
main magnetic contactor (rated for 250 VAC/
1 Amp or 30 VDC/1 Amp).
Control Power Terminal Block (TB2) for Model 8720MC-RPS027
and 8720MC-RPS065
The table below describes the terminals on the control power
terminal block (TB2) for Model 8720MC-RPS027 and
8720MC-RPS065.
Main Power Terminal Block (TB1) for Model 8720MC-RPS027 and
8720MC-RPS065
The table below provides the information of the terminals on use of
the terminals on the main power terminal block (TB1) for Model
8720MC-RPS027 and 8720MC-RPS065.
Terminal Name
Main Power
Terminals
DC Bus Terminals
Grounding Terminal
Symbol
L
1
, L
2
, L
3
P, N
G
Description
To connect three-phase AC input power to
the main circuit.
For 460 V unit: 380 to 460 VAC +10%,
-15%, 50/60 Hz +/-5%
To connect the 8720MC-RPS Regenerative
Power Supply to load equipment.
To ground the 8720MC-RPS Regenerative
Power Supply.