Port status indicator, Mod status indicator, Port status indicator mod status indicator – Rockwell Automation 2100-ENET CENTERLINE 2100 Motor Control Centers EtherNet/IP Network Adapter User Manual
Page 58
58
Rockwell Automation Publication 2100-UM006A-EN-P - July 2013
Chapter 7
Troubleshooting
PORT Status Indicator
This red/green bicolor status indicator indicates the status of the adapter’s
connection to the end device.
MOD Status Indicator
This red/green bicolor status indicator indicates the status of the adapter.
Table 8 - Status Indicators and Descriptions
Status Indicator
Description
Page
PORT
End Device Connection Status
MOD
Adapter Status
NET A
EtherNet/IP network Connection Status
NET B
EtherNet/IP network Transmit Status
Status
Cause
Corrective Action
Off
The adapter is not powered or is not properly connected to
the end device.
Securely connect the adapter to the end device by using the 2100-ENET
adapter to DeviceNet cable.
Verify there are 24V DC across the two terminals on the green connector.
Flashing Red
The adapter is not receiving a ping message from the end
device.
Verify that cables are securely connected and not damaged. Replace cables
if necessary.
Cycle power to the end device and verify the end device powers up; for the
E3 Plus module, there is a green flash and then a red flash on powerup.
Steady Red
The end device has refused an I/O connection from the
adapter.
Important: Cycle power to the adapter after making any of the following
corrections:
Verify that the end device is supported by the adapter (that it is an E3 Plus
or 825-P at the appropriate firmware revisions. See
Steady Orange
The adapter is connected to a product that is not supported.
Connect the adapter to a product that is supported by the adapter (for
example, an E3 Plus or 825-P at the appropriate firmware revisions).
Flashing Green
The adapter is establishing an I/O connection to the end
device.
No action required.
Steady Green
The adapter is properly connected and is communicating
with the end device.
No action required.
Status
Cause
Corrective Action
Off
The adapter is not powered or is not properly connected to
the end device.
• Securely connect the adapter to the end device by using the 2100-ENET
adapter to DeviceNet cable.
• Verify there are 24V DC across the two terminals on the green
connector.
Flashing Red
The adapter has failed the firmware test.
The adapter is being upgraded.
• Cycle power to the end device.
• If cycling the power does not correct the problem, update the firmware
to the latest firmware release.
Steady Red
The adapter has failed the hardware test.
• Cycle power to the adapter.
• Replace the adapter.
Flashing Green
The adapter is operational, but is not transferring I/O data to
a controller.
• Place the scanner in RUN mode.
• Program the controller to recognize and transmit I/O to the adapter.
• Configure the end device for the program in the controller.
Steady Green
The adapter is operational and transferring I/O data to a
controller.
No action required.