Rockwell Automation 61C544A RTD Module User Manual
Page 35
![background image](/manuals/580590/35/background.png)
4Ć19
Register 3003= Reserved for future use.
Register 3004= Register contains the RTD channel's Number of
Samples. This value is provided by the data table in
the 5000Ćseries registers.
Register 3005= Register contains the RTD channel's High High
alarm value. This value is provided by the data table
in the 5000Ćseries registers.
Register 3006= Register contains the RTD channel's High alarm
value. This value is provided by the data table in the
5000Ćseries registers.
Register 3007= Register contains the RTD channel's Low alarm
value. This value is provided by the data table in the
5000Ćseries registers.
Register 3010= Register contains the RTD channel's Low Low alarm
value. This value is provided by the data table in
the 5000Ćseries registers.
Register 3011= Register contains the RTD channel's configuration
command. This value is provided by the data table
in the 5000Ćseries registers.
Registers 3100 to 3137= Registers contain the data read from the
RTD module.
Registers 5000 to 5027= Registers contain the data used to
configure the RTD channels. Each
channel uses six registers:
Not
# of
High
Low
Configure
Not
Used
# of
Samples
High
High
High Low
Low
Low
Configure
Command
Reg. 5000 = 0 0
20
2500
2000 1000 500
12288*
Reg. 5010 = 0 0
20
2500
2000 1000 500
12288ă
Reg. 5020 = 0 0
20
2500
2000 1000 500
12288ă
* 12288 = 3000 Hex
Note that you must use the POINT MONITOR function to enter these
values into the 5000Ćseries registers before you begin executing the
program.
Register 5200= Register contains the value (0) for the READY
command.