Rockwell Automation 61C544A RTD Module User Manual
Page 21
4Ć5
4.1.3
High Alarm Status Register (Register 17)
Register 17 indicates the current status of each configured channel's
High alarm. See figure 4.3. A bit is set in this register whenever a
channel's input value exceeds the configured High alarm limit. The
bit is reset when the input value returns to a level below the
configured limit.
Bit 0ă=ăChannel 0
Bit 5ă=ăChannel 5
Bit 10ă=ăChannel 10
Bit 1ă=ăChannel 1
Bit 6ă=ăChannel 6
Bit 11ă=ăChannel 11
Bit 2ă=ăChannel 2
Bit 7ă=ăChannel 7
Bit 12ă=ăChannel 12
Bit 3ă=ăChannel 3
Bit 8ă=ăChannel 8
Bit 13ă=ăChannel 13
Bit 4ă=ăChannel 4
Bit 9ă=ăChannel 9
Bit 14ă=ăChannel 14
Bit 15ă=ăChannel 15
Register 17
Bits 0Ć15
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
15 14 13
12 11 10 9
8
7
6
5
4
3
2
1
0
Figure 4.3 Ć High Alarm Status Register
4.1.4
Low Alarm Status Register (Register 18)
Register 18 indicates the current status of each configured channel's
Low alarm. See figure 4.4. A bit is set in this register whenever a
channel's input value is less than the configured Low alarm limit. The
bit is reset when the input value returns to a level above the
configured limit.
Register 18
Bits 0Ć15
Bit 0ă=ăChannel 0
Bit 5ă=ăChannel 5
Bit 10ă=ăChannel 10
Bit 1ă=ăChannel 1
Bit 6ă=ăChannel 6
Bit 11ă=ăChannel 11
Bit 2ă=ăChannel 2
Bit 7ă=ăChannel 7
Bit 12ă=ăChannel 12
Bit 3ă=ăChannel 3
Bit 8ă=ăChannel 8
Bit 13ă=ăChannel 13
Bit 4ă=ăChannel 4
Bit 9ă=ăChannel 9
Bit 14ă=ăChannel 14
Bit 15ă=ăChannel 15
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
Figure 4.4 Ć Low Alarm Status Register