H automate program command register table, Appendix h, Automate program command register table – Rockwell Automation 61C613 16 Channel Analog Input Module User Manual
Page 47
![background image](/manuals/580566/47/background.png)
HĆ1
Appendix H
AutoMate Program Command
Register Table
REGISTER
DATA
ADDRESS
COMMENTS
20,000
0049
M+ 0
RESET
20,001
0000
M+ 1
NOOP
20,002
0000
M+ 2
NOOP
20,003
0000
M+ 0
INTIALIZE SETUP
20,004
0000
M+ 1
SETUP
20,005
0000
M+ 2
SETUP
20,006
0020
M+ 0
WRITE CHANNEL REGISTER
20,007
WWWW
M+ 1
CHANNEL NUMBER
20,010
0000
M+ 2
DISABLE AUTOĆINCREMENT ON
CHANNEL NUMBER
20,011
0010
M+ 0
CONFIGURE CHANNEL INPUT
20,012
XXXX
M+ 1
TYPE OF ANALOG INPUT (SEE TABLE)
20,013
0000
M+ 2
NOOP
20,014
0016
M+ 0
CONFIGURE CHANNEL SLOPE
20,015
YYYY
M+ 1
LOW ORDER BYTE
20,016
ZZZZ
M+ 2
HIGH ORDER BYTE
20,017
0018
M+ 0
CONFIGURE CHANNEL OFFSET
20,020
YYYY
M+ 1
LOW ORDER BYTE
20,021
ZZZZ
M+ 2
HIGH ORDER BYTE
20,022
0004
M+ 0
CONFIGURE SCAN RANGE
20,023
0000
M+ 1
START AT CHANNEL 0
20,024
0015
M+ 2
STOP AT CHANNEL 15*
20,025
0000
M+ 0
INITIALIZE SCAN
20,026
0000
M+ 1
NOOP
20,027
0008**
M+ 2
60 HZ,CENTIGRADE, 16 BIT MODE
CONTINUOUS SCAN
20,030
0024
M+ 0
READ ANALOG INPUT CHANNEL
20,031
0000
M+ 1
CHANNEL NUMBER POINTER
20,032
0000
M+ 2
NOOP
* USER MUST DEFINE THE LAST CHANNEL USED; DEFAULT IS 15 IN THIS
CASE.
** 0008 =
1 0 0 0
ąąąąPOWER LINE FREQUENCY; 0 Ć 60Hz, 1 Ć 50Hz
ąąąTEMPERATURE UNITS
0 = CENTIGRADE, 1 = FARENHEIT
Note: This is only used with the T/C kind codes.
ąąDATA ACQUISITION MODE
0 = ONĆCOMMAND, 1 = CONTINUOUS SCAN