PanelView 300 Micro Terminal 21

41061-156-01(A)

No communications with
computer.

1. Communications Comm

fault.

2. Incorrect baud rate or

communication settings.

3. Incorrect terminal node or

max node address.

4. Computer fault.
5. Communications driver not

properly loaded.

1. Check Comm indicator. See

page 19.

2. Verify computer and

terminal are at same baud.

3. Verify node addresses.

4. Refer to computer manual.
5. Refer to RSLinx online help

or manual.

Application filename appears
as ****** on Terminal Info
screen.

1. Application file invalid.

2. Application unusable

because of error.

1. Download application to

terminal.

2. Download new application.

Screen objects not visible.

1. Correct power not applied.
2. Contrast not set correctly.

3. Terminal in screen saver

mode.

1. Verify power connections.
2. Access Screen Setup from

Configuration Mode and
adjust display contrast.

3. Access Screen Setup from

Configuration Mode to
check if terminal is in Screen
Saver Mode.

Values do not update on
display but appear as asterisks
****

1. Terminal not communicating

with logic controller.

2. Value is invalid or exceeds

the field width for object.

1. Check status of Comm

indicator. See problem “No
communication with
controller” for details.

2. Change the field width set

for the object.

LCD display is difficult to view. 1. Display contrast level set

incorrectly.

1. Access Configuration mode

and adjust the display
contrast level.

Can’t Configuration Mode
when pressing Left and Right
arrow keys simultaneously.

1. Left and right arrow keys are

assigned to screen objects
in the terminal application.

1. Contact Technical Support

for assistance.

No network found.

1. Node setting of controller

does not match application.

2. Controller data file does not

have enough elements.

1. Change node address in

application to match
controller node address.

2. Verify data file elements for

all tag addresses.

Problem

Causes

Corrective Action