PanelView 300 Micro Terminal 19

41061-156-01(A)

Comm and Fault Indicators

The PanelView 300 Micro has a Comm (communication) and Fault (error) status
indicator. These indicators are visible from Configuration Mode when selecting
the Communication screen. Use the Comm and Fault indicators to isolate
operating problems.

Indicator

State

Indicates

Comm

ON (steady state solid fill)

Normal Operating (no communications fault)

OFF (no fill)

Fault detected. Verify:
• controller is in run mode.
• communication settings for terminal and

controller.

• terminal and controller node addresses.
• terminal to controller connections.

Blinking (flashing)

No communications established. For DF1 terminals,
the Comm indicator flashes until an application is
loaded.

Fault

OFF (no fill pattern)

Normal operating state

ON (steady state solid fill)

Fault detected. Reset or cycle power to the terminal.
If the fault remains the terminal requires servicing.

Blinking (flashing)

Hardware is functioning but no application is loaded
in the terminal or the current application is
corrupted. Reload the application file into the
terminal.

DF1 - Full Duplex

Comm

Fault

PanelView Online

F3 MORE

F4 EXIT

C

F2 RESET VIDEO

F

F1 RUN MODE

Language
Communication
Preset Operations

CONFIGURATION MODE