Using the decimal point – Rockwell Automation 2711E-ND1 Reference Manual PanelBuilder 1400e User Manual
Page 98
92
Numerics
Publication 2711E-6.15 – November 1998
Rung for DH+ or ControlNet Application
20384
MOV
MOVE
SOURCE: N7:11
DEST: N7:12
Enter Bit
N7:10
] [
1
EQU
EQUAL
SOURCE A N7:13
SOURCE B 0
To select which value to change, press the Interlocked Push Button beside
the value, and use the Numeric Keypad to enter the new value.
You can determine whether or not the operator can enter numbers
with decimal points in the scratchpad for the Numeric Keypad
Enable Button, Numeric Input Cursor Point, and Numeric Entry
Keypad objects.
Note: With the exception of the Implicit decimal point option, any
decimal point entered is implied only. With the Implicit option, a
floating-point value is written to the PLC. For all other decimal point
options, the value sent to the Keypad Numeric Input control is
stripped of the decimal point.
Choose from the following decimal point options:
•
Disabled specifies no values with decimal points can be entered
in the scratchpad. Only integer values can be entered.
•
Implicit allows the operator to enter the number and decimal
point. Unlike the Decimal Key Controlled option, Implicit does
not use a (Numeric) Decimal Point Position control. The Keypad
Numeric Input control, which uses a floating-point address in the
PLC, contains all the information.
Implicit (floating-point) numbers are accurate up to 7 significant
digits. Leading or trailing zeroes do not count as significant
digits. If there are more than 7 significant digits, the number is
rounded off. The following table illustrates how the PanelView
terminal calculates the number of significant digits.
Number Entered
Number of Significant Digits
Number sent to the
PLC
ББББББ
ББББББ
.000012
БББББББББ
БББББББББ
2
БББББББ
БББББББ
.000012
.000012345678
8
.00001234568
ББББББ
ББББББ
123.45000
БББББББББ
БББББББББ
5
БББББББ
БББББББ
123.45
ББББББ
ББББББ
123.45678
БББББББББ
БББББББББ
8
БББББББ
БББББББ
123.4568
Using the Decimal Point
"