beautypg.com

2 bus error – Rockwell Automation 57C411 Resolver Input Module User Manual

Page 33

background image

5Ć3

To test local I/O, first replace the input module. Next,

replace the processor module (s). If the problem persists,

take all of the modules except one processor module and

the input module out of the backplane. If the problem is

now corrected, one of the other modules in the rack is

malfunctioning. Reconnect the other modules one at a

time until the problem reappears. If none of these tests

reveals the problem, replace the backplane.
To test remote I/O, first verify that the remote I/O system is

communicating with the drop that contains the input

module being tested. Next, by systematically swapping

out modules, determine whether the input module is the

only module that is not working.
If more than one module is not working correctly, the

problem most likely lies in the remote I/O system. Refer to

the the DCS 5000 Remote I/O Instruction Manual (JĆ3629)

for additional information. If the problem does not lie in the

system, it probably involves the remote rack.
To test the remote rack, first replace the input module. If

the problem persists, take all of the modules out of the

remote backplane except the slave remote I/O module

and the input module. If the problem is now corrected,

one of the other modules in the rack is malfunctioning.

Reconnect the other modules one at a time until the

problem reappears. If the problem proves to be neither in

the remote I/O system nor in the remote rack, try replacing

the backplane.

5.2

Bus Error

Problem: A 31" or 16" appears on the processor module's LED.

This error message indicates that there was a bus error when the

system attempted to access the module. The possible causes of this

error are a missing module, a module in the wrong slot, or a

malfunctioning module. It is also possible that the user has attempted

to write to the wrong registers on the module. Use the following

procedure to isolate a bus error:
Step 1.

Verify that the input module is in the correct slot and that

the I/O definitions are correct.
Refer to figure 3.2. Verify that the slot number being

referenced agrees with the slot number defined in the

configuration task. Verify that the register number is in the

range of 0Ć4.
For remote I/O installations, also verify that the master slot

and remote drop number are defined correctly.
Refer to the DCS 5000 Remote I/O Instruction Manual

(JĆ3629) for more information on configuring your remote

I/O system.

Step 2.

Verify that the module can be accessed.
Connect the programming terminal to the system and run

the ReSource Software. Use the I/O MONITOR function to

display the four registers on the input module. If the

programmer is able to monitor the inputs, the problem lies

in the application software (refer to step 3). If the