Rockwell Automation 57C411 Resolver Input Module User Manual

Page 14

background image

3Ć2

Step 4.

Mount the terminal strip (from cable assembly M/N

57C373) on a panel. The terminal strip should be mounted

to allow easy access to the screw terminals. Be sure that

the terminal strip is close enough to the rack so that the

cable will reach between the terminal strip and the

module. The cable assembly is approximately 60 inches

long.

Step 5.

Attach the resolver but leave the mechanical coupling

between the resolver and the motor unconnected.
Fasten the field wires from the resolver to the terminal

strip. Typical field connections are shown in figures 3.2

and 3.3.
Use twistedĆpair wire, connected as shown, for the cabling

between the resolver and the terminal strip in the control

enclosure. Recommended twistedĆpair wire is Beldent

9497 cable or equivalent. Maximum operating cable length

is dependent upon the type of cable you use.
Make certain that all field wires are securely fastened.

ă1
ă2
ă3
ă4
ă5
ă6
ă7
ă8
ă9
10

REFERENCE

SINE

COSINE

M/N 57C360 RESOLVER

FROM MODULE

TO MODULE

REFERENCE VOLTAGE: 26 Vrms

SINE VOLTAGE: 11.8 Vrms

COSINE VOLTAGE: 11.8 Vrms

Terminal Strip

in Control

Enclosure

R1

R2

S1

S3

S2

S4

Figure 3.2 Ć Typical M/N 57C360 Resolver Field Connections